Table 2: Installer Configuration Menu (Part 5 of 7)
Parameter
Description and Default
Appearing
on Display
Disables heating stage(s) operation
5
H lock
when the outside air temperature is
greater than the configured value. If
the fan mode is set to Auto or
Smart, the fan output is also
disabled. Requires that an outside
air temperature sensor be installed
and connected.
Default: 120°F/49°C
5
Disables cooling stage(s) operation
C lock
when the outside air temperature is
less than the configured value. If the
fan mode is set to Auto or Smart,
the fan output is also disabled.
Requires that an outside air
temperature sensor be installed and
connected.
Default: -40°F/-40°C
Unocc TM
Sets the time delay between the
moment when the thermostat
controller toggles from the Occupied
mode to the Unoccupied mode after
the last motion is detected by the
occupancy sensor.
Default: 0.5 hours
2
Sets the number of events within a
2/4event
24-hour period.
Default: 2.0
Aux cont
Energizes peripheral devices
(lighting equipment, exhaust fans,
and economizers).
Default: n.o.
Note: The contact toggles with the
internal Occupied/Unoccupied
schedule (or the NSB contact on
one of the digital inputs, if used).
Provides the desired occupied
2
Prog rec
temperature either at the start of the
Occupied schedule or after the
Occupied schedule begins.
Default: off
Note: Progressive recovery is
disabled if either DI1 or DI2 is
configured as remote NSB.
T600HPx-4 and T600HPx-4+PIR Series Heat Pump Thermostat Controllers Installation Instructions
Selection Options
Range: -15°F/-26°C to 120°F/49°C adjustable in 5F°/5C° increments
Range: -40°F/-40°C to 95°F/35°C adjustable in 5F°/5C° increments
Range: 0.5 hours to 24.0 hours adjustable in 0.5 hour increments
(4.0): Four events (two Occupied and two Unoccupied) within a
24-hour period
(2.0): Two events (one Occupied and one Unoccupied) within a
24-hour period
(n.c.): Contact open = Occupied; contact closed = Unoccupied
(n.o.): Contact closed = Occupied; contact open = Unoccupied
(on): Enabled (provides the desired occupied temperature at the
start of the Occupied schedule)
(off): Disabled (provides the desired occupied temperature after the
Occupied schedule begins)