Ending Temporary Temperature Setpoints; Selecting The System Mode - Johnson Controls TEC22 4-3 Series Installation Instructions Manual

Lonworks networked multi-stage economizer thermostats
Table of Contents

Advertisement

Table 3: Entering Permanent Temperature
Setpoints (Part 1 of 2)
Thermostat
Description
Display
Press the MENU key while in the
Status Display Menu to enter the
RoomTemp
Main User Menu.
75.0°F
Press the NO key to all prompts until
the temperature setpoint prompt
Temperat
appears on the display (it may be the
set? Y/N
first prompt). Press the YES key to
enter the temperature setting menu.
Press the YES key to change the
occupied cooling setpoint. Press the
Cooling
NO key to advance to the occupied
set? Y/N
heating setpoint menu.
Press the UP/DOWN arrow keys to
set the temperature. Press the YES
Cooling
key to store the value and advance to
75.0 ° F
the next menu.
Press the YES key to change the
occupied heating setpoint. Press the
Heating
NO key to advance to the unoccupied
set? Y/N
cooling setpoint menu.
Press the UP/DOWN arrow keys to
set the temperature. Press the YES
Heating
key to store the value and advance to
68.0 ° F
the next menu.
Press the YES key to change the
unoccupied cooling setpoint. Press
Unocc CL
the NO key to advance to the
set? Y/N
unoccupied heating setpoint.
Press the UP/DOWN arrow keys to
set the temperature. Press the YES
Unocc CL
key to store the value and advance to
80.0 ° F
the next menu.
Press the YES key to change the
unoccupied heating setpoint. Press
Unocc HT
the NO key to advance to the
set? Y/N
temperature display units.
Press the UP/DOWN arrow keys to
set the temperature. Press the YES
Unocc HT
key to store the value and advance to
62.0 ° F
the next menu.
TEC22x4-3 L
W
® Networked Multi-Stage Economizer Thermostats Installation Instructions
ON
ORKS
Table 3: Entering Permanent Temperature
Setpoints (Part 2 of 2)
Thermostat
Description
Display
Press the YES key to set the display
units to °F or °C. Press the NO key to
° F/ ° C
advance to the temperature setpoint
set? Y/N
type menu.
Press the YES key to return to the
Status Display Menu or press the NO
Exit?
key to reenter the temperature
Y/N
setting menu.
Note: Whether the thermostat is heating or cooling,
the respective setpoint is temporarily adjusted. To
toggle between the temporary heating and cooling
setpoints, press the NO key while changing the
temporary setpoints.

Ending Temporary Temperature Setpoints

The temporary setpoints remain in effect for the
duration set in the TOccTime parameter or until
manually released.
To release the temporary setpoint sooner, while in the
Main User Menu:
1. Press the YES key to the first prompt that appears.
2. If the thermostat does not immediately return to the
Status Display Menu, press the MENU key again
and press the YES key to exit the Main User Menu.
The setpoint reverts to the Permanent Temperature
Setpoint.

Selecting the System Mode

The thermostat has four system modes:
Automatic Mode (auto): Automatic changeover
between heating and cooling. This is the default
setting.
Cooling Mode (cool): Cooling operation only
Heating Mode (heat): Heating operation only
Off Mode (off): The thermostat is off; however,
when frost protection (Frost pr parameter) is
enabled, the thermostat still calls for heat
(if required).
To set the system mode while in the Main User Menu:
1. Press the NO key to all prompts until the system
mode prompt appears on the display. Press the
YES key to select the desired system mode.
11

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tec2264-3Tec2204-3

Table of Contents