Procedure Of Self-Diagnosis By Led; Troubleshooting By Led On The Indoor Unit's - Daikin SkyAir Super Inverter 70 D Series Service Manual

Split system air conditioners d series;
Table of Contents

Advertisement

SiE25-110

5. Procedure of Self-Diagnosis by LED

5.1

Troubleshooting by LED on the Indoor Unit's

Foreword
Troubleshooting can be carried out by service monitor LED (green). (Blinks when normal)
4
Notes:
1. When the INSPECTION/TEST button of remote controller is pushed, INSPECTION display
2. In the INSPECTION mode, when the ON/OFF button is pushed and held for 5 seconds or
3. Operation halts due to malfunction depending on the model or condition.
4. If LED-B is off, the transmission wiring between indoor and outdoor unit may be incorrect or
5. Troubleshoot by turning off the power supply for a minimum of 5 seconds, turning it back on,
Troubleshooting
: LED on
3
: LED off
5
Microcomputer
Transmission
Normal Monitor
Normal Monitor
HAP (LED-A)
HBP (LED-B)
5
5
4
3
blinks entering INSPECTION mode.
more, the aforementioned malfunctioning history display is off. In this case, after the
malfunction code blinks 2 times, the code display turns to "00" (=Normal) and the unit No.
turns to "0". The INSPECTION mode automatically switches to the normal mode (set
temperature display).
disconnected. Before performing the previously described troubleshooting, check the
transmission wiring.
and then rechecking the LED display.
: LED blinks — : No connection with troubleshooting
Indoor unit normal → Outdoor unit trouble shooting
5
Incorrect transmission wiring between indoor and
4
outdoor unit
If outdoor unit's LED-A is off, proceed outdoor unit's
3
trouble shooting. If outdoor unit's LED-A blinks, failure of
wiring or indoor or outdoor unit P.C board ass'y. (Note 4)
Failure of indoor unit PC board ass'y (Note 5)
Malfunction of power supply or failure of PC board ass'y
or broken transmission wire between indoor and outdoor
unit. (Note 5)

Procedure of Self-Diagnosis by LED

Contents/Processing
127

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Skyair super inverter 70Skyair r-407c

Table of Contents