Daikin Inverter FLXS25BVMB Installation Manual

R410a split series
Hide thumbs Also See for Inverter FLXS25BVMB:

Advertisement

INSTALLATION
MANUAL
R410A Split Series
Models
FLXS25BVMB
FLXS35BVMB
FLXS50BVMB
FLXS60BVMB
FLX25BVMB
FLX35BVMB
FLKS25BVMB
FLKS35BVMB
FLKS50BVMB
FLKS60BVMB
FLK25BVMB
FLK35BVMB
Installationsanleitung
Split-Baureihe R410A
Manuel d'installation
Montagehandleiding
R410A Split-systeem
Manual de instalación
Manuale d'installazione
Serie Multiambienti R410A
Εγχειρßδιο εγκατÜστασηò
διαιροýìενηò σειρÜò R410A
Manual de Instalação
Рóêоводство по монтажó
Серия R410A с раздельной óстановêой

Installation manual

English
R410A Split series
Deutsch
Français
Série split R410A
Nederlands
Español
Serie Split R410A
Italiano
ΕλληνικÜ
Portugues
Série split R410A
Рóссêий

Advertisement

Table of Contents
loading

Summary of Contents for Daikin Inverter FLXS25BVMB

  • Page 1: Installation Manual

    Deutsch Split-Baureihe R410A Manuel d’installation Français Série split R410A Montagehandleiding Nederlands R410A Split-systeem Manual de instalación Models Español Serie Split R410A FLXS25BVMB FLKS25BVMB Manuale d’installazione FLXS35BVMB FLKS35BVMB Italiano Serie Multiambienti R410A FLXS50BVMB FLKS50BVMB Εγχειρßδιο εγκατÜστασηò ΕλληνικÜ διαιροýìενηò σειρÜò R410A FLXS60BVMB...
  • Page 2 2SB63219-13...
  • Page 3: Safety Precautions

    Safety Precautions • Read these Safety Precautions carefully to ensure correct installation. • This manual classifies the precautions into WARNINGS and CAUTIONS. Be sure to follow all the precautions below: they are all important for ensuring safety. WARNINGS ....Failure to follow any of WARNING is likely to result in such grave consequences as death or serious injury. CAUTIONS ....Failure to follow any of CAUTION may in some cases result in grave consequences.
  • Page 4: Choosing A Site

    Accessories – Indoor unit Heat insulation tube Mounting plate AAA dry-cell batteries (Extension auxiliary pipe) Heat insulation tube Photocatalytic deodorizing filter Side covers (Refrigerant pipe) Air purifying filter Operation manual Binding bands Wireless remote controller Installation manual Extension auxiliary pipe Remote control holder •...
  • Page 5: Before Installing The Indoor Unit

    Before Installing the Indoor Unit Perform the following before installing the indoor unit. 1) Open the air inlet grille and the screw cover, and remove the 7 screws. 2) Release the claws in the 3 places indicated. 3) Release the center hook and remove the front panel. Screw cover Electric 4) Release the claws in the 2 places indicated and remove...
  • Page 6: Indoor Unit Installation Drawings

    Indoor Unit Installation Drawings There should be no space Space for installation work between ceiling and the unit. Min. (200 mm) Space for installation work Min. (200 mm) 50 mm or more Air filters from walls Mounting plate The mounting plate should be installed on a wall which can M4 ×...
  • Page 7: Ceiling Mounting

    Indoor Unit Installation Drawings Ceiling mounting. Local drain pipe Rear side pipinghole ø65 mm Ceiling Ceiling Wall *1 Determine the position of the Rear side drainhose hole ø40 mm feed-through hole so that the local piping is placed in a 1,050 downward sloping direction.
  • Page 8: Indoor Unit Installation

    Indoor Unit Installation Ceiling Mounting Installing The Suspension Bolt. 1) Install the suspension bolt so that it can support the indoor unit; adjust distance to ceiling before installation. 2) Mount the indoor unit according to the installation drawings and tighten it securely with M10 nut. (4 places) 3) After mounting the indoor unit on the ceiling, install each part as shown in the diagram on the right.
  • Page 9 Indoor Unit Installation Wall Mounting Installation • Install the indoor unit on the wall according to the installation drawings. 1) Hang the indoor unit on the hooks of A mounting plate. (2 places) 2) Fix the three holes in the lower portion of the indoor unit with M4 × 25L screws. Mounting plate J Side cover (6 claws)
  • Page 10 Installing Indoor Unit 1) Connect the extension auxiliary pipe ( , supplied) to the local pip- Note: ing. Remove the bottom frame cover for right-back piping before installing the indoor unit. (Applies to both ceiling mounting and wall mounting units.) 2) Prepare the local piping at the connection point for the drain pipe, as shown in the installation drawings.
  • Page 11: Drain Piping

    Indoor Unit Installation Insulation of Refrigerant Pipes After checking for refrigerant leaks • Joints in liquid pipe and the gas pipe must be insulated with heat insulation tube attached with binding bands. • Cut heat insulation tube to appropriate length. Binding band Heat insulation tube Drain Piping...
  • Page 12: Refrigerant Piping Work

    Refrigerant piping work , install as described in the installation manual supplied with the Multi outdoor unit. With a Multi indoor unit Flaring the pipe end. (Cut exactly at 1) Cut the pipe end with a pipe cutter. right angles.) Remove burrs 2) Remove burrs with the cut surface facing down- Flaring...
  • Page 13 Refrigerant piping work 2-2. Selection of Copper and Heat Insulation materials • When using commercial copper pipes and fittings, observe the following: Inter-unit wiring 1) Insulation material: Polyethylene foam Gas pipe Heat transfer rate: 0.041 to 0.052kW/mK (0.035 to 0.045 kcal/mh°C) Liquid pipe Refrigerant gas pipe’s surface temperature reaches 110°C max.
  • Page 14: Trial Operation And Testing

    Trial Operation and Testing Trial Operation and Testing. 1-1 Measure the supply voltage and make sure that it falls in the specified range. 1-2 Trial operation should be carried out in either cooling or heating mode. I I I I For Heat pump •...
  • Page 15 2P098794-2V M02B074C (0408) HT...