Detailed Explanation Of Setting Modes - Daikin SkyAir Super Inverter 70 D Series Service Manual

Split system air conditioners d series;
Table of Contents

Advertisement

Method of Field Set (Reset after Maintenance Inspection/Repair)
1.5

Detailed Explanation of Setting Modes

1.5.1 Air Flow Adjustment - Ceiling height
Make the following setting according to the ceiling height. The setting position No. is set to "01"
at the factory.
Ceiling
Height
Ceiling
Height
1.5.2 Air Flow Direction Setting
Set the air flow direction of indoor units as given in the table below. (Set when optional air outlet
blocking pad has been installed.) The second code No. is factory set to "01."
Setting Table
1.5.3 Filter Sign Setting
If switching the filter sign ON time, set as given in the table below.
Set Time
Setting
Contamination Light
Contamination Heavy
∗1 FHYCP only 5,000 hrs., ∗2 FHYCP only 2,500 hrs.
46
In the Case of FAYP
Mode No.
Setting Switch
No.
13(23)
0
In the Case of FHYCP (50 ~ 71 class), FUYP
01 Standard (N)
02 High Ceiling
(H)
03 Higher Ceiling
(S)
In the Case of FHYCP (100 ~ 140 class)
01 Standard (N)
02 High Ceiling
(H)
03 Higher Ceiling
(S)
Mode No.
First Code No.
13 (23)
1
Filter Specs.
01
02
Setting Position
No.
01
Wall-mounted type: Standard
02
Wall-mounted type: Slight increase
03
Wall-mounted type: Normal increase
No. of Air Outlets Used
4-way Outlets
Lower than 2.7 m
Lower than 3.0 m
Lower than 3.0 m
Lower than 3.3 m
Lower than 3.5 m
Lower than 3.5 m
No. of Air Outlets Used
4-way Outlets
Lower than 3.2 m
Lower than 3.6 m
Lower than 3.6 m
Lower than 4.0 m
Lower than 4.2 m
Lower than 4.2 m
Second Code
No.
01
F : 4-direction air flow
02
T : 3-direction air flow
03
W : 2-direction air flow
Standard
200 hrs.
100 hrs.
Setting
3-way Outlets
2-way Outlets
Lower than 3.5 m
Lower than 3.8 m
3-way Outlets
2-way Outlets
Lower than 4.2 m
Lower than 4.2 m
Setting
Long Life
Ultra Long Life Filter
2,500 hrs. ∗1
10,000 hrs.
1,100 hrs. ∗2
5,000 hrs.
SiE25-110
Field Setting