Daikin SkyAir Super Inverter 70 D Series Service Manual page 220

Split system air conditioners d series;
Table of Contents

Advertisement

SiE25-110
Step
3. Removing the float switch
1
Reverse the drain pump
mounting plate which
was removed according
to the procedure
described on the
preceding page.
2
Remove the 1 screw,
displace the float switch
sideward, then
dismount the float
switch.
[Installation procedure of
drain pump or float switch]
1
Install a spare drain
pump or float switch on
the mounting plate,
then firmly secure the
lead wires using the
provided clamp
materials (3 pieces).
2
Connect the lead wires
of the drain pump or
float switch in the
original state, firmly
secure the
aforementioned clamp
materials (screw type
fixing) to the drain pan
with the use of
mounting screws.
Removal Procedure
Procedure
FHYCP71~140D
Points
When removing the float
switch, cut the following
clamp materials.
Clamp material securing the
drain pump lead wire to the
drain pump mounting plate.
Clamp material bundling the
drain pump lead wire and
float switch lead wire.