Function Details
Condensation
Avoidance
Control (FHYP
Model Only)
Note
1. Regardless of thermostat ON or OFF, the control can be functioned with the operation mode
2. The function is not provided for models other than FHYP71~125B.
Outdoor Unit
If the indoor unit is for both a heat pump and cooling only type, this function differentiates
Identification
whether the outdoor unit is functioning as a heat pump or cooling only unit, and automatically
decides the which operation modes can be set.
Function
Heat pump : Fan / cool / dry / auto / heat
Drain Pump
1. During cooling and program dry operation modes, the control function turns on the drain
Control (FHYCP
and FHYP
2. During cooling and microcomputer-controlled operation modes as well as in the initial stage
(OPTION) Only)
(A) Drain pan water level detection system (water level sensor type) : cassette type
i) During operation startup
Drain pan
Compressor
Drain pump
Error processing
76
Continuous 30 minutes operation of cooling
After continuous 30 minutes of operation with downward
horizontal blade position, change the blade position to
level, and after one hour, the unit operation can be reset.
of " cooling ( automatic cooling ) " or " programmed drying ".
Operation modes which can be set
pump according to the compressor operation. When the compressor turns OFF, the drain
pump continues operating for additional 5 minutes.
of heating operation, the control function detects the water level in the drain pan, and
performs an error shutdown process if the water level is abnormal.
Water level abnormality
Normal
ON
OFF
ON
OFF
Abnormal
Normal
One hour drying
The unit operation can be reset with changing operation
mode into "heating" or "fan", changing air flow direction or
turning "ON" or "OFF" the unit operation.
ON operation
Note 2)
1 min
3 min
2 min 5 sec
SiE25-110
(S1117)
5 min
Function and Operation