Self-Diagnosis By Wired Remote Control - Daikin ALTHERMA HT ERSQ 011 AA Service Manual

Table of Contents

Advertisement

Troubleshooting by Remote Control
2.2

Self-diagnosis by Wired Remote Control

Explanation
If operation stops due to malfunction, the remote control's operation LED blinks, and malfunction code is
displayed. (Even if stop operation is carried out, malfunction contents are displayed when the inspection
mode is entered.) The malfunction code enables you to tell what kind of malfunction caused operation to
stop. See page 137 for malfunction code and malfunction contents.
Note:
1. Pressing the INSPECTION/TEST button will blink the check indication.
2. While in check mode, pressing and holding the ON/OFF button for a period of five seconds or more
3. Subcode is needed to indicate which refrigerant system is causing the error.
132
Inspection display
Malfunction code
with subcode
Inspection/Test button
will clear the failure history indication shown above. In this case, on the codes display, the malfunction
code will blink twice and then change to "00" (=Normal), the Unit No. will change to "0", and the
operation mode will automatically switch from check mode to normal mode (displaying the set
temperature).
ESIE09-08A
Operation LED
ON/OFF button
Troubleshooting

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents