Maintenance Mode Setting

Procedure
1. Enter the field set mode.
2. Enter the maintenance mode.
3. Select the mode No.
4. Select the unit No.
5. Carry out the necessary settings for each mode. (Modes 41, 44 and 45)
6. Enter the setting contents. (Modes 44 and 45)
7. Return to the normal operation mode.
Table
Mode
No.
40
41
43
44
45
Operation is not reset by malfunction code reset for inspection.
(Cannot be reset because the count is updated each time a malfunction occurs.)
64
Continue to push the inspection / test operation button for a minimum of 4 seconds.
After having entered the field set mode, continue to push the inspection / test operation
button for a minimum of 4 seconds.
Set the desired mode No. with the up/down temperature setting button.
Select the indoor unit No. set with the time mode START/STOP button.
See the table below for details.
Enter by pushing the timer ON/OFF button.
Tap the inspection / test operation button one time.
Function
Content and Operation
Method
Malfunction
You can change the history
Hysteresis
with the programming time up-
down button.
Sensor Data
Select the display sensor with
Display
the programming time up-
down button
Display sensor
00 Remote control sensor
01 Suction
02 Heat exchange
Forced Fan
Turns the fan ON for each unit
ON
individually.
Individual
Sets fan speed and air flow
Setting
direction for each unit
individually when using group
control.
Settings are made using the
"air flow direction adjust" and
"fan speed adjust" buttons.
Unit No.
Changes unit No.
Change
Set the unit No. after changing
with the programming time up-
down button.
Example of Remote Controller Display
SiE25-110
Field Setting