5 Advanced Operations

5-22-3 Using Status Display Messages (E5GC Only)

You can display status display messages using the work bits. While one or more of the work bits (WR1
to WR8) is ON, the message for the highest bit number that is ON is alternately displayed with the cor-
responding bit number.
Status display messages are displayed when WR (status display message) is selected for the PV status
display or SV status display function (Advanced Function Setting Level).
You can set status display messages with CX-Thermo version 4.62 or higher.
Example: When Work Bit 1 (WR1) Is ON for the PV Status Display Function (Registered Message:
WR1)
5 - 72
3. Select Library 1 from the
library list, and then click the
OK Button.
Confirm the following
settings, and then click the
OK Button.
Work bit 1 operation type:
Operation 1
Work bit 1 input assignment
A = 7: Alarm 1
Work bit 1 input assignment
B = 19: Invert for RUN/STOP
Work bit 1 input assignment
C = 0: Always OFF
Work bit 1 input assignment
D = 0: Always OFF
Auxiliary output 1 = Work bit
1
4. Closing the Logic Operation
Editor Dialog Box
Click the Close Button.
This completes the
procedure for setting
parameters using the
CX-Thermo. Transfer the
settings to the Digital
Controller to set the Digital
Controller. Refer to
CX-Thermo help for the
procedure to transfer the
settings.