6 Parameters
lbab
• This parameter sets the LBA band.
• If a control deviation greater than the LBA band is not reduced when the LBA level is
exceeded, an loop burnout is detected.
Function
Temperature input
Setting
Analog input
Related Parameters
See
See
Process Value/Set Point (Operation Level): Page 6-8
Alarm 1 to 4 Type (Initial Setting Level): Page 6-47
LBA Detection Time (Advanced Function Setting Level): Page 6-77
LBA Level (Advanced Function Setting Level): Page 6-77
6 - 78
LBA Band
Setting range
0.0 to 999.9
0.00 to 99.99
A Standard Model must be used.
Alarm 1 must be assigned.
The alarm type must be set to 12 (LBA).
The LBA detection time must not be 0.
Unit
°C or °F
%FS
E5@C Digital Temperature Controllers User's Manual (H174)
Default
3.0
0.20