2-2-3

E5EC/E5AC Terminal Block Wiring Example

Terminal Arrangement
The terminals block is divided into five types of terminals: control outputs 1 and 2, sensor input, auxiliary
outputs, input power supply, and options.
Input Power Supply
Control outputs 1 and 2
Auxiliary Outputs
Precautions for Correct Use
• When you purchase the Digital Controller, it will be set for a K thermocouple (input type = 5). If
a different sensor is used, an input error (s.err) will occur. Check the setting of the Input Type
parameter.
Control Outputs 1 and 2
Model Numbers
The specifications for control outputs 1 and 2 are given in the following location in the model number.
E5@C-@@ @ @ @ M-@@@
Code
RX
1 relay output
QX
1 voltage output (for driving SSR)
CX
1 linear current output
QQ
2 voltage outputs (for driving SSRs)
QR
1 voltage output (for driving SSR) and
1 relay output
RR or PR
2 relay outputs
CC
2 linear current outputs
CQ
1 linear current output and 1 voltage
output (for driving SSRs)
E5@C Digital Temperature Controllers User's Manual (H174)
1
2
3
4
5
6
7
8
9
10
11
12
Control outputs 1 and 2
Output type
Not used.
25
13
26
14
Options
27
15
16
28
17
29
18
30
31
19
32
20
33
21
34
22
35
Sensor input
23
36
24
250 VAC, 5 A (resistive load)
12 VDC, 40 mA
4 to 20 mA DC or 0 to 20 mA DC with load of 500 Ω
max.
12 VDC, 21 mA
12 VDC, 21 mA for voltage output
250 VAC, 5 A (resistive load) for relay output
250 VAC, 5 A (resistive load)
4 to 20 mA DC or 0 to 20 mA DC with load of 500 Ω
max.
4 to 20 mA DC or 0 to 20 mA DC with load of 500 Ω
max. for current output and 12 VDC, 21 mA for voltage
output
2 Preparations
Specification
2
2 - 23