5 Advanced Operations
This procedure sets the MV change rate limit to 5.0%/s. The related
parameters are as follows:
PID ON/OFF = PID
ST = OFF
Operating Procedure
• Setting 2-PID Control
1
Press the M Key several times in the Initial Setting Level to
display cntl (PID ON/OFF).
2
Press the U or D Key to select pid (PID).
The default is onof (ON/OFF control).
• Turning OFF Self-tuning
1
Press the M Key several times in the Initial Setting Level to
display st (ST: self-tuning).
2
Press the U or D Key to set the value to off.
The default is on.
• Setting the MV Change Rate Limit
1
Press the M Key several times in the Adjustment Level to dis-
play orl (MV Change Rate Limit).
2
Press the U or D Key to set the value to 5.0.
The default is 0.0 (%/s).
5 - 54
Initial Setting Level
cntl
onof
cntl
pid
Initial Setting Level
st
st
off
Adjustment Level
orl
orl
E5@C Digital Temperature Controllers User's Manual (H174)
PID ON/OFF
ST
on
MV Change
Rate Limit
0.0
5.0