Omron E5C series User Manual page 372

Digital temperature controllers
Hide thumbs Also See for E5C series:
Table of Contents

Advertisement

A Appendices
Parameters
Characters
sub1
Auxiliary Output 1
Assignment
sub2
Auxiliary Output 2
Assignment
sub3
Auxiliary Output 3
Assignment
sub4
Auxiliary Output 4
Assignment
000
alma
Integrated Alarm
Assignment
t-u
000
Soak Time Unit
alsp
Alarm SP Selection
000
rs-t
Remote SP Input
000
rspu
Remote SP Enable
000
A - 28
Setting (monitor) value
NONE: No assignment
O: Control output (heating)
C-O: Control output (cooling)
ALM1: Alarm 1
ALM2: Alarm 2
ALM3: Alarm 3
ALM4: Alarm 4
HA: Heater alarm (HB + HS)
HB: Heater burnout alarm (HB)
HS: Heater short alarm (HS)
S.ERR: Input error
RS.ER: RSP input error
*3
P.END: Program end output
RUN: RUN output
ALM: Integrated alarm
*4
WR1: Work bit 1
*4
WR2: Work bit 2
*4
WR3: Work bit 3
*4
WR4: Work bit 4
*4
WR5: Work bit 5
*4
WR6: Work bit 6
*4
WR7: Work bit 7
*4
WR8: Work bit 8
Same as the Auxiliary Output 1 Assignment
parameter.
Same as the Auxiliary Output 1 Assignment
parameter.
Same as the Auxiliary Output 1 Assignment
parameter.
0 to 255
Alarm 1: +1
Alarm 2: +2
Alarm 3: +4
Alarm 4: +8
HB alarm: +16
HS alarm: +32
Input error: +64
RSP input error: +128
M: Minutes
H: Hours
*6
S: Seconds
SP-M: Ramp set point
SP: Set point
4-20: 4-20 mA
0-20: 0-20 mA
1-5V: 1-5 V
0-5V: 0-5 V
0-10: 0-10 V
OFF, ON
Display
Default
none
ALM1
*Digital
o
Controllers
c-o
without HB
alm1
and HS
alm2
alarm
alm3
detection:
HA
alm4
ha
hb
hs
s.err
rs.er
p.end
run
alm
wr1
wr2
wr3
wr4
wr5
wr6
wr7
wr8
Same as the
ALM2
Auxiliary
Output 1
Assignment
parameter.
Same as the
ALM3
Auxiliary
Output 1
Assignment
parameter.
Same as the
ALM4
Auxiliary
Output 1
Assignment
parameter.
49
m, h
M
sp-m, sp
SP-M
4-20, 0-20,
4-20
1-5V, 0-5V,
0-10
off, on
OFF
E5@C Digital Temperature Controllers User's Manual (H174)
Unit
None
None
None
None
None
None
None
None
None

Advertisement

Table of Contents
loading