6 Parameters
t-u
• Set the soak time unit for the simple program function.
Function
s: Seconds,* m: Minutes, h: Hours
Setting
*
Related Parameters
See
See
Program Start (Operation Level): Page 6-12
Soak Time Remain (Operation Level): Page 6-13
Soak Time (Adjustment Level): Page 6-31
Wait Band (Adjustment Level): Page 6-32
Program Pattern (Initial Setting Level): Page 6-46
alsp
This parameter sets whether the set point that triggers the alarm is the ramp SP or target SP.
Setting
Related Parameters
SP Ramp Set Value and SP Ramp Fall Value (Adjustment Level): Page 6-33
See
See
ST (Self-tuning) (Initial Setting Level): Page 6-45
6 - 82
000
Soak Time Unit
Setting range
Seconds can be selected only with the E5GC.
000
Alarm SP Selection
Setting range
sp-m: Ramp SP, sp: SP
The Program Pattern parameter must not be set to
OFF.
Default
m
Alarm 1 to alarm 4 must be assigned.
The SP Ramp Set Value parameter must not be set
to OFF and the SP Ramp Fall Value parameter must
not be set to SAME or OFF. The ST parameter must
be set to OFF.
The alarm type must be set to 1, 2, 3, 4, 5, 6, 7, 14,
15, 18, or 19.
Default
sp-m
E5@C Digital Temperature Controllers User's Manual (H174)