Clearances; Mantel & Trim; Alcove; Clearance Requirements - Jøtul GF 400 BV Sebago Installation And Operation Instructions Manual

Natural vent gas stove
Table of Contents

Advertisement

Stove and Vent

Clearance Requirements

Minimum Clearances from the Stove
to Combustibles
See figs. 2-3.
Rear:
3" (76 mm) - measured from Draft Hood
Ceiling:
32 1/4" (819 mm) - measured from stove top
Corner:
3" (76 mm) - measured from stove top
Sides:
3" (76 mm - measured from stove top)
Venting
All sides: 1" (25 mm)
All vent components must be installed in accordance with
the manufacturer's instructions and within the terms of
their listing. Refer to the manufacturer's instructions for
approved clearances from the vent pipe to combustible
materials.
Minimum Alcove Dimensions
Maintain clearances to combustibles as noted above.
Width:
32" (81 cm)
Depth:
24" (61 cm)
Height:
61" (155 cm)
Approved Wall Pass-Through
Use only 4" Simpson Dura-Vent Wall Thimble #3143 to
pass the vent pipe through combustible walls. See fig. 2.
13 "
33 cm
4 3/4"
12 cm
Figure 2. Approved Wall Pass-Through, Simpson Dura-Vent
Wall thimble #3134.
3 7/8" to 8"
9.8 cm to 20.3 cm
13 "
33 cm
3"
(76 mm)
Figure 2. Parallel Installation Clearances.
3"
(76 mm)
Figure 3. Vent adaptor centerline at minimum clearance
to corner walls.
Mantel Clearances -
Stove shown with standard legs. With Short Legs, subtract
2 1/4" (51 mm) from the clearances indicated below.
55 1/4”
52.25”
49 1/4”
140 cm
133 cm
125 cm
53 3/4”
50 3/4”
136.5 cm
129 cm
Figure 4. Mantel and Trim specifications -
Stove installed with Top Plate flush with fireplace face.
138301_Rev_G 10.4.11
3"
(51 mm)
To Rear Wall
3"
(76 mm)
9 1/2"
(251 mm)
9 1/2"
(251 mm)
3"
(76 mm)
Max. Mantel
Depth
12.5”
10.25”
8”
5.75”
Min. Mantel
3.5”
Max. Trim
Depth = 1”
47 3/8”
(120 cm)
Depth
28 1/2”
72.3 cm
7

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents