Option Selection / Call Waiting
*91
Disable & ADT Pulse Enable
Entry 1: Options
0 = none
1 = Bell Supervision Processing†
4 = using Audio Alarm Verification
(AAV) unit
8 = Enable Exit delay restart/reset ††
U L
1. UL installations using the AAV
feature must use the ADEMCO
UVCM module (part of ADEMCO
UVS system).
2. Bell supervision is required for fire
alarm installations.
3. Exit delay restart/reset must be
disabled.
FOR SIA INSTALLATIONS: Exit delay
should be enabled.
Multiple choice example: for both AAV
and Exit delay restart, enter # + 12 (4 +
8); for all (1 + 4 + 8), enter # + 13.
Entry 2: Call Waiting Disable / ADT
Pulse Enable
0 = Call Waiting not used / Pulse
disabled
1 = Call Waiting disable digits (*70)
entered in field *40
2 = Pulse enabled
3 = Call Waiting disable and Pulse
enabled
Phone Line Monitor Enable
*92
Entry 1–Timeout:
0 = disabled
1-15 = 1 minute to 15 minutes
respectively
(2 = 2 min, 3 = 3 min, etc.;
# = 10 = 10 min, # + 11 min = 11,
# + 12 = 12 min, # + 13 = 13 min,
# + 14 = 14 min, # + 15 = 15 min)
Entry 2–Display/Sound:
0 = touchpad display only when phone
line is faulted.
1 = touchpad display plus touchpad
trouble sound when line is faulted.
Each partition turns off its own
trouble sound. No automatic timeout.
2 = Same as "1" plus programmed
output device STARTS. If either
partition is armed, external sounder
activates. External sounder will be
turned off by normal bell timeout, or
by security code plus OFF from
either partition (it does not have to
be the one that was armed).
Entry 1: Options
Select the desired options by adding the values of each desired
option.
† If bell supervision is selected, you must also cut the red PCB
jumper.
††"Exit Delay Restart/reset" option allows use of the [∗] key to
restart the exit delay at any time when the system is armed
STAY or INSTANT. This feature also enables automatic exit
delay reset, which, when the system is armed in AWAY mode,
restarts exit delay if the entry/exit door is re-opened and
closed before the original exit delay time expires. This
automatic exit delay reset occurs only once during an armed
away period.
IMPORTANT: AAV should not be used when Paging or
Alarm Reports are sent to a secondary number unless the
monitoring zone option is used (which pauses calls).
Otherwise, the call to the secondary number by the
communicator after the alarm report will prevent the AAV
from taking control of the telephone line, and the AAV "Listen
in" session cannot take place.
Entry 2: Call Waiting Disable / ADT Pulse Interactive
Solutions Enable
Call Waiting Disable: If call waiting is used, the call
waiting cancel digits must be entered in field *40 PABX Code
or Call Waiting Disable, and the call waiting disable option
must be enabled ("1") in entry 2. When selected, the system
dials the entry in field *40 only on alternate dial attempts;
this allows proper dialing in the event call waiting service is
later canceled by the user.
ADT Pulse Enable: Enables ADT Pulse Interactive
Solutions, if used.
Entry 1: Sets the length of time a phone line fault must
remain after detected before the second digit option is
activated.
Entry 2: Selects the desired phone line fault response.
Option 2 may be used even if a relay unit or Powerline carrier
device is not connected to the control.
Programmed Output Device must either be programmed to be
STOPPED in field ∗80 or STOPPED by entry of [security
code] + [#] + 8 + device number. Partition in ∗80 should be set
to "0," for STOP.
U L Field *92 must be enabled for fire alarm installations, UL
commercial burglar alarm installations and UL residential
burglar alarm installations.
If the control unit is used on a UL commercial burglar alarm
system which requires 2 methods of remote communication,
then the control unit's DACT and the other method of signal
transmission must monitor each other against communication
failure and line fault. The fault must be received and
annunciated within 200 seconds of its occurrence.