ADT Safewatch Pro 3000EN Installation And Setup Manual page 32

Hide thumbs Also See for Safewatch Pro 3000EN:
Table of Contents

Advertisement

3000EN Series: Installation Instructions
Type 06
24-hour Silent Alarm
Type 07
24-hour Audible Alarm
Type 08
24-hour
Auxiliary Alarm
Type 09
Supervised Fire
Type 10
Interior w/Delay
Type 12
Monitor Zone
Type 14
24 Hour Carbon
Monoxide Monitor
Type 16
Fire w/Verification
Type 20
Arm-Stay (BR only)
Type 21
Arm-Away (BR only)
Type 22
Disarm (BR only)
Type 23 *
No Alarm Response
Type 24
Silent Burglary
3-4
• Usually assigned to a zone containing an emergency button.
• Sends a report to the central station but provides no touchpad display or
sounding.
• Assign to a zone that has an emergency button.
• Sends a report to the central station, and provides an alarm sound at the
touchpad, and an audible external alarm.
• Assign to a zone containing an emergency button, or to a zone containing
monitoring devices such as water or temperature sensors.
• Sends a report to the central station and provides an alarm sound at the
touchpad. (No bell output is provided.)
• Provides a fire alarm on short circuit and a trouble condition on open circuit. A
fire alarm produces a pulsing bell output.
• This zone type is always active and cannot be bypassed.
• Provides entry delay (using the programmed entry time), if tripped when the
panel is armed in the Away mode.
• Entry Delay 1 begins whenever sensors in this zone are violated, regardless of
whether or not an entry/exit delay zone was tripped first.
• Bypassed when the panel is armed in the Stay or Instant modes; if armed in
Night-Stay mode, zones assigned to zone list 05 (night-stay zone list) are not
bypassed when system armed in Night-Stay mode.
• Works as a dynamic monitor of a zone fault/trouble (not alarm). In the case of a
short/open, the message, "*ALARM*-24 Hr. Non-Burg. -#XXX " (where XXX is the
zone number) will be sent to the Central Station. The system touchpad will
display a "check" message indicating the appropriate zone (but touchpad beeping
does not occur). Upon restoral of the zone, the message, "*RESTORE*-24 Hr.
Non-Burg. -#XXX " will be sent to the Central Station.
• The "check" message will automatically disappear from the touchpad dynamically,
when the zone restores; a user code + off sequence is not needed to reset the zone.
• Faults of this zone type are independent of the system, and can exist at the time
of arming without interference.
• Since this is a "trouble" zone type, do not use this zone type with relays set to
activate upon "alarm."
• Assigned to any zone with a carbon monoxide detector.
• A carbon monoxide alarm produces touchpad and detector sounding (does not
affect bell output).
• Always active and cannot be bypassed.
• Provides a fire alarm when zone is shorted, but only after alarm verified.
• System verifies alarm by resetting smoke detectors after short is detected
(removes power 7 seconds for zone 1; 3 seconds for trigger output). A subsequent
short circuit within 90 seconds triggers fire alarm.
• Provides a trouble response when zone is open.
• Arms the system in Stay mode when the zone is activated.
• Pushbutton units send the user number to the central station when arming or
disarming.
• User number for button must be assigned.
• Arms the system in Away mode when the zone is activated.
• Pushbutton units send the user number to the central station when arming or
disarming.
• User number for button must be assigned.
• Disarms the system when the zone is activated.
• User number for button must be assigned.
• Can be used on a zone when an output relay action is desired, but with no
accompanying alarm (e.g., lobby door access).
• Usually assigned to all sensors or contacts on exterior doors and windows where
bells and/or sirens are NOT desired.
• Provides an instant alarm, with NO audible indication at any touchpad or
external sounder, if the zone is faulted when the system is armed in the Away,
Stay, or Instant, modes.
• A report is sent to the central station.