4.2
Mounting ST 3000 Transmitter,
Flush mounting
ATTENTION
34
ST 3000 Release 300 and SFC Model STS103 User's Manual
To mount a flush mounted model, cut a hole for a 1" standard pipe in
the tank or pipe where the transmitter is to be mounted. Weld the 1"
mounting sleeve to the wall of the tank or to the hole cut on the pipe.
Insert the meter body of the transmitter into the mounting sleeve and
secure with the locking bolt. Tighten the bolt to a torque of 6,4 Nm +/-
0,30 Nm (4.7 ft-lbs +/- 0.2 ft.-lbs.). Figure 11 shows a typical
installation for a transmitter with a flush mount on a pipe.
Once the transmitter is mounted, the electronics housing can be rotated
to the desired position. See Table 9, Step 4 for details.
On insulated tanks, remove enough insulation to accommodate the
mounting sleeve.
Figure 11
Typical Flush Mounted Transmitter Installation
Continued
1" Pipe Mount -
316 SS Weld Nipple
(standard option)
Continued on next page
February 2012