Honeywell ST 3000 User Manual page 79

Smart transmitter release 300 and smart field communicator model sts103
Hide thumbs Also See for ST 3000:
Table of Contents

Advertisement

6.2
Overview,
What to configure,
continued
Table 20
Summary of Pressure Transmitter Configuration Parameters, continued
Configuration Data
Failsafe Mode
The following parameters are only for transmitters with optional Local Smart Meter.
Meter Engineering Units
Engineering Units High and
Low
February 2012
ST 3000 Release 300 and SFC Model STS103 User's Manual
Continued
NOTE: This parameter is valid only to select the failsafe action for the
STDC card in a controller - not the transmitter. If you are using
the STDC card to interface with the ST 3000 transmitter, contact
Honeywell Technical Assistance in using this parameter.
ATTENTION An STIMV IOP module has built-in failsafe capabilities
and ignores this parameter.
If the transmitter is set for LINEAR output conformity, you can choose to
have the Local Smart Meter display pressure readings in one of these
engineering units:
"H2O_39F
PSI
mmHg_0C
KPa
Custom
%
If the transmitter is set for SQUARE ROOT output conformity, you can
choose to have the Local Smart Meter display flow readings in one of
these engineering units:
GPM
GPH
You can enter desired lower and upper (high) display limits to scale flow
(GPM, GPH) or Custom engineering units to represent the transmitter's
0 to 100% output within the meter's display range of 19,990,000.
ATTENTION When the transmitter is set to SQUARE ROOT output
conformity, the lower display limit for flow units (GPM, GPH) and Custom
unit must equal zero (0).
Setting or Selection
MPa
BAR
Kg/cm^2
mBAR
g/cm^2
mmH2O_4C
Custom
%
inHg_32F
mH2O_4C
Continued on next page
65

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents