6.7
Setting Range Values Using SFC,
Procedure 2
Table 26
Setting LRV and URV to Applied Pressures
Step
Press Key
1
2
E
LRV
0%
3
G
SET
4
NON-VOL
ENTER
(Yes)
5
6
F
URV
100%
7
G
SET
8
NON-VOL
ENTER
(Yes)
82
ST 3000 Release 300 and SFC Model STS103 User's Manual
Table 26 gives the procedure for setting range values to sample applied
pressures.
Read Display or Action
Apply known input pressure to
transmitter that represents LRV for 0%
(4 mAdc) output.
L R V
1
P T
"
5 .
Ø Ø Ø Ø
L R V
1
P T
S E T
L
L R V
1
P T
S
F
C
W
O R K
I
L R V
1
P T
7 .
8 3 7 7
"
Apply known input pressure to
transmitter that represents URV for
100% (20 mAdc) output.
U R V
1
P T
"
4
7
.
8 3 7
U R V
1
P T
S E T
U
U R V
1
P T
S
F
C
W
O R K
I
U R V
1
P T
5
5
.
4 8 2
Continued
Present LRV setting. (Pressure for 4
3 Ø 1 1
mAdc (0%) output.)
H 2 O _ 3 9 F
Prompt asks if you want to set LRV
3 Ø 1 1
to applied pressure. If you don't
R V
?
want to set LRV, press [
exit function. Otherwise, go to Step
4.
Message exchange is working.
3 Ø 1 1
N G
.
.
.
Applied LRV setting stored in
3 Ø 1 1
H 2 O _ 3 9 F
transmitter's working memory.
Present URV setting. (Pressure for
3 Ø 1 1
20 mAdc (100%) output.)
H 2 O _ 3 9 F
Prompt asks if you want to set URV
3 Ø 1 1
to applied pressure. If you don't
R V
?
want to set URV, press [
exit function. Otherwise, go to Step
8.
Message exchange is working.
3 Ø 1 1
N G
.
.
.
Applied URV setting stored in
3 Ø 1 1
transmitter's working memory.
Description
] key to
CLR
] key to
CLR
Continued on next page
February 2012