Honeywell ST 3000 User Manual page 103

Smart transmitter release 300 and smart field communicator model sts103
Hide thumbs Also See for ST 3000:
Table of Contents

Advertisement

6.8
Setting Range Values Using Local Adjustments,
Continued
Procedure, continued
February 2012
ST 3000 Release 300 and SFC Model STS103 User's Manual
Table 27
Setting Range Values Using Local Zero and Span
Adjustments, continued
Step
a. Press and hold SPAN button on Local Zero and Span assembly or
9
Local Smart Meter.
ATTENTION The Local Smart Meter readings revert to the default
unit of percent (%) during this operation. If the error code Er0
appears on the display, you are working with a model STD110
transmitter that does not support the Local Zero and Span
adjustments. If the error code Er4 appears, you are trying to set a
SPAN value that is outside acceptable limits for your transmitter.
Readjust applied pressure to be within acceptable range limits and
repeat this procedure.
b. Press Increase  button once to complete this function.
ATTENTION
second and then returns reading 100%.
Display goes
blank for 1/2
second and
returns with
100% reading
c. Check that milliammeter reading equals 20 mA and release SPAN
button.
ATTENTION
are not working with a model STD110 transmitter that ignores local
adjustments. The Local Smart Meter readings return to the set
engineering units after you release the SPAN button.
Action
VAR
SEL.
Press &
%
0
Hold
SPAN
9
9
.
ANALOG
ZERO
The Local Smart Meter display goes blank for a 1/2
VAR
SEL.
%
0
SPAN
1
0
0
.
ANALOG
ZERO
If milliammeter reading doesn't change, be sure you
UPPER
VALUE
100
UNITS
0
%
SET
LOWER
VALUE
UPPER
VALUE
100
UNITS
0
%
SET
LOWER
VALUE
Press once
Continued on next page
89