Daikin Super Multi NX C-Series Service Manual page 191

Super multi nx c-series
Table of Contents

Advertisement

Troubleshooting
Troubleshooting
Check No.4
Refer to P.205
Check No.6
Refer to P.207
180
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Check the wiring and piping.
Wiring or piping out of spec?
NO
Check No. 4
Check the electronic expansion
valve.
Motor functioning?
YES
Check No. 6
Check the outdoor unit heat
exchanger thermistor.
Thermistor as specified
in its characteristic
chart?
YES
Check No. 6
Check the room temperature
thermistor.
Thermistor as specified
in its characteristic
chart?
YES
Change the gas to let moisture out
of the unit (after drawing a
vacuum).
Error again?
NO
YES
NO
NO
NO
YES
SiE12-411
Activate the wiring error
check mode.
Replace the defective Ev or
coil.
Replace the heat
exchanger thermistor.
Replace the room
temperature thermistor.
Replace the room
temperature thermistor or
indoor unit heat exchanger
thermistor.
Do the vacuum-drying.
Replace the indoor unit
PCB and then start the
wiring error check mode.
(R3059)
Service Diagnosis

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents