Low-Voltage Detection - Daikin Super Multi NX C-Series Service Manual

Super multi nx c-series
Table of Contents

Advertisement

Troubleshooting

5.24 Low-voltage Detection

U2
Remote
Controller
Display
Outdoor Unit LED
A
Display
Method of
An abnormal voltage rise or drop is detected by checking the detection circuit or DC voltage
Malfunction
detection circuit.
Detection
" An over-voltage signal is fed from the over-voltage detection circuit to the microcomputer, or
Malfunction
Decision
Conditions
" The system will be shut down if the error occurs 16 times.
" Clearing condition: Continuous run for about 60 minutes (normal)
" Supply voltage not as specified
Supposed
" Over-voltage detector or DC voltage detection circuit defective
Causes
" PAM control part(s) defective
Troubleshooting
202
5
1
4
2
1
3
1
4
the voltage being detected by the DC voltage detection circuit is judged to be below 150 V
for 0.1 second.
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Check the supply voltage.
Supply voltage as
specified?
YES
Turn on the
power again.
System restarted?
NO
Repeat a
couple of times.
4
NO
(Precaution before turning on the power again)
Make sure the power has been off for
at least 30 seconds.
YES
Disturbance factors
∗ Noise ∗ Power supply distortion
SiE12-411
Correct the power supply.
Check for such factors for a
long term.
∗ Try to get restarted a
couple of times.
Replace the SPM.
(Replace the outdoor unit
PCB.)
(R2854)