Control Specification
3.8

Fan Control

Outline
Fan control is carried out according to the following priority.
1. Fan ON control for electric component cooling fan
2. Fan control when defrosting
3. Fan OFF delay when stopped
4. ON/OFF control when cooling operation
5. Fan control when the number of heating rooms decreases
6. Tap control when drooping function is working
7. Fan control when forced operation
8. Fan control in indoor / outdoor silent operation
9. Fan control in the powerful mode
10. Fan control for pressure difference upkeep
Detail
Fan OFF Control when Stopped
" Fan OFF delay for 60 seconds must be made when the compressor is stopped.
Fan control when the number of heating room decreases (Only for Heat Pump Model)
When the outdoor air temperature is more than 10°C, the fan must be turned OFF for 30
seconds.
Tap Control in Indoor / Outdoor Unit Silent Operation
1. When Cooling Operation
2. When Heating Operation
3.9

Moisture Protection Function 2

Outline
In order to obtain the dependability of the compressor, the compressor must be stopped
according to the conditions of the temperature of the outdoor air and outdoor heat exchanger.
Detail
Heat Pump Model
" Operation stop depending on the outdoor air temperature
Compressor operation turns OFF under the conditions that the system is in cooling operation
and outdoor air temperature is below –10°C.
Cooling Only Model
" Operation stops depending on the outdoor air temperature.
Compressor operation turns OFF under the condition that outdoor air temperature is below
–10°C (10°C for R22 type).
94
When the outdoor air temperature is less than 37°C, the fan tap must be set to L.
When the outdoor air temperature is more than 4°C, the fan tap must be turned to L (only for
heat pump model).