5.
Heat Pump Module Location: Select the location for the heat pump
module.
The heat pump module must be positioned such that there is a clearance
of at least 300 mm perpendicular from the air inlet louvres and the outlet
grilles.
The heat pump module must be installed against a wall and on a level slab
or solid base with a minimum size of 600 mm wide x 600 mm deep.
The heat pump flow and return lines connecting the heat pump storage
tank to the heat pump module must not exceed four (4) metres in length
each and must not contain more than 4 x 90º bends each. All changes in
direction of the pipe work must be made using bends. The pipe work
should not contain elbows.
Ensure the cable set reaches the storage tank with sufficient length to
enable it to be saddle clamped to the wall.
Ensure the maximum length of the heat pump flow and return pipe
work and the maximum number of 90° bends will not be exceeded.
and allow for at least 300 mm ventilation clearance
Step 5
select location for heat pump module
HEAT PUMP AND TANK ASSEMBLY
15