Main Functions
1.6
Fan Speed Control
Control Mode
The airflow rate can be automatically controlled depending on the difference between the set
temperature and the room temperature. This is done through phase control and
For more information about Hall IC, refer to the troubleshooting for fan motor on page 116.
Phase Steps
Phase control and fan speed control contains 9 steps: LLL, LL, SL, L, ML, M, MH, H and HH.
In automatic fan speed operation, the step "SL" is not available.
LLL
LL
L
ML
M
MH
H
HH (POWERFUL)
Note:
1. During POWERFUL operation, fan operates H tap + 50 rpm.
2. Fan stops during defrost operation.
3. In time of thermostat OFF, the fan rotates at the following speed.
Automatic
On heating mode, the indoor fan speed will be regulated according to the indoor heat exchanger
Airflow Control
temperature and the difference between the room temperature and the required set point.
for Heating
Automatic
The following drawing explains the principle of fan speed control for cooling:
Airflow Control
for Cooling
Note:
*In automatic fan speed operation, upper limit is at M tap in 30 minutes from the operation start.
COMFORT
AIRFLOW Mode
8
for Indoor Units
Step
= The airflow rate is automatically controlled within this range when the FAN setting
button is set to automatic.
Cooling: The fan keeps rotating at the set tap.
Heating: The fan stops.
Dry: The fan will stop after keeps rotating for a few minutes at LL tap.
fan speed
+2.5˚C
+1.5˚C
+0.5˚C
Thermostat
setting
temperature
The airflow rate is controlled automatically within the following steps.
Cooling: L tap – MH tap (same as AUTOMATIC)
Heating: ML tap – MH tap
The latest command has the priority between POWERFUL and COMFORT AIRFLOW.
Cooling
(R6833)
MH*
+2˚C
M
+2˚C
ML
+1˚C
L
Phase control
SiBE12-908
Hall IC
Heating
(R6834)
Difference between room
and set temperature
(R8301)
Function and Control
control.