Daikin CTXU25G2V1B Service Manual page 14

Inverter multi system with humidifying g-series
Hide thumbs Also See for CTXU25G2V1B:
Table of Contents

Advertisement

SiBE12-908
How to Check the
You can check whether the humidifying unit is in good working order. If you set HUMID HEAT
test operation (refer to the installation manual for details), you can check even beyond the range
Motion of
of the conditions for humidifying operation.
Humidifying
1. Hygroscopic fan .......................... Air is exhaled from the front exhaust outlet of outdoor unit.
Operation
2. Humidifying fan/heater/damper ... Warm air is blown from the duct of outdoor unit.
3. Humidification rotor ..................... The rotor is rotating with top panel off.
As for the performance, estimate from psychrometric chart with the measured temperature and
humidity of the outdoor air and of the humidified air (in front of the indoor outlet) using thermal
hygrometer.
Humidity
At HUMID HEAT operation, as room temperature rises, relative humidity is temporarily lowered.
This is because as room temperature rises, relative humidity is lowered even if the moisture
Fluctuation
by
content is the same.
Temperature
Settings
e.g.) The rise in the room temperature from 15°C to 25°C will result in the fall in humidity from
40%RH to about 22%RH.
As humidifying operation starts concurrently with heating, humidity rises gradually as shown in
the figure below.
Some room conditions (floor space, ventilation frequency, number of residents, etc.) and
temperature settings (mostly higher settings) may result in unsatisfactory humidity settings.
Humidity
Function and Control
3
Airflow rate (m
/min)
0.38
Humidity Fluctuation on HUMID HEAT Operation
(%)
100
90
"HUMID HEAT" start
80
When room temperature rises,
70
relative humidity is lowered
even if the moisture
content is same.
60
50
40
30
20
10
0
20
Measurement Conditions
Outdoor temp.: 7
HUMID HEAT operation setting:
Temp.; each setting as below, Humidity; "CONT" (Continuous)
Airflow rate setting: H tap
Area of the room: 26.4 m²
Humidifying hose length: 4.0 m
Ventilation: 0.75 times/hour
0.5 times of natural ventilation
0.25 times of humidity absorption by a carpet, a curtain, etc.
40
60
Main Functions
Setting temp.
17
20
23
Humidity rises
gradually.
Heating
without humidifying
setting temp. 23
80
100
Time (min.)
(R9411)
11

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

2mxu50gv1bCtxu35g2v1bCtxu42g2v1bCtxu50g2v1b2mxu40gv1b

Table of Contents