Daikin CTXU25G2V1B Service Manual page 118

Inverter multi system with humidifying g-series
Hide thumbs Also See for CTXU25G2V1B:
Table of Contents

Advertisement

SiBE12-908
Troubleshooting
Check No.02
Refer to P.162
Service Diagnosis
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Check the air passage.
Is there any short-circuit?
NO
Check the intake air filter.
Is it very dirty?
NO
Check the dust accumulation on
the indoor unit heat exchanger.
Is it very dirty?
NO
Check No. 02
Indoor unit heat exchanger
thermistor check
Does it
conform to the
thermistor characteristic
chart?
NO
YES
YES
YES
YES
Troubleshooting
Provide sufficient air passage.
Clean the air filter.
Clean the heat exchanger.
Replace the indoor unit PCB.
Replace the thermistor
(replace the indoor unit PCB).
(R9464)