Troubleshooting
2.33
Outdoor Unit PCB Abnormality
Circuit Abnormality
U4
Remote
Controller Display
Outdoor Unit LED
A5
Display
Method of
Detect within the programme of the microcomputer that the programme is in good running
order.
Malfunction
Detection
Malfunction
1. When the programme of the microcomputer is in bad running order.
2. When indoor-outdoor unit signal transmission can not be performed for more than 15 sec.
Decision
3. When zero-cross signal can not be detected for more than 10 sec.
Conditions
Supposed
Causes
150
5 -
Display disabled due to power supply fault
Communication circuit fault in outdoor unit PCB
Out of control of microcomputer caused by external factors
Noise
Momentary voltage drop
Momentary power loss
Defective outdoor unit PCB
Defective thermal fuse in outdoor terminal board
or
Communication
SiBE12-908
Service Diagnosis