Fan Speed Control For Indoor Unit - Daikin FVXG25K2V1B Service Manual

Inverter pair floor standing type
Hide thumbs Also See for FVXG25K2V1B:
Table of Contents

Advertisement

SiBE061121_A
1.4

Fan Speed Control for Indoor Unit

Outline
Phase control and fan speed control contains 9 steps: LLL, LL, SL, L, ML, M, MH, H, and HH.
The airflow rate can be automatically controlled depending on the difference between the room
thermistor temperature and the target temperature. This is done through phase control and Hall
IC control.
For more information about Hall IC, refer to the troubleshooting for fan motor on page 66.
Automatic Fan
In automatic fan speed operation, the step "SL" is not available.
Speed Control
LLL
LL
L
ML
M
MH
H
HH (POWERFUL)
<Cooling>
The following drawing explains the principle of fan speed control for cooling.
<Heating>
In heating operation, the fan speed is regulated according to the indoor heat exchanger
temperature and the difference between the room thermistor temperature and the target
temperature.
Note:
1. During POWERFUL operation, the fan rotates at H tap + 50 rpm.
2. The fan stops during defrost control.
Function and Control
Step
Cooling
= The airflow rate is automatically controlled within this range when the [FAN] setting
button is set to automatic.
Fan speed
+2.5°C
+1.5°C
+0.5°C
Heating
(R11681)
(R6834)
Room thermistor temperature – target temperature
MH
+3°C
M
+2°C
ML
+1°C
L
Main Functions
(R14635)
21