Control Specification
3.4.5
Compressor Protection Function
When turning the compressor from OFF to ON, the upper limit of frequency must be set as
follows. (The function must not be used when defrosting.)
32
40 class 50 class
FCG 1
62
55
FCG 2
72
70
FCG 3
90
85
TCG 1
140
150
TCG 2
180
180
TCG 3
300
300