Buderus Logano plus GB312 Installation And Service Instructions Manual page 59

Gas condensing boiler
Table of Contents

Advertisement

1)
Type
Display code Fault code
V
CO
568
V
CO
569
V
CY
573
V
CY
574
V
LP
570
Table 23 Fault displays
1) V = interlocking; B = inhibiting; BC = operating code
Logano plus GB312 – 6 720 806 273 (2013/01)
Cause
Description
Water pressure sensor fault
Water pressure sensor
(cable break).
break (voltage > 3.5 V).
Water pressure sensor fault
Water pressure sensor
(short-circuit).
short-circuit (voltage
< 0.5 V).
Flow temperature
The control unit receives
unrealistic values from
< 23 °F (< -5 °C) (circuit
the supply temperature
break)
sensor.
Flow temperature
The control unit receives
unrealistic values from
>266°F (>130°C) (short-
the supply temperature
circuit)
sensor.
Too many resets via the
Too many resets have
interface.
been received via the
interface within a certain
period.
Important: this fault can
be reset only by the
button on the SAFe.
Troubleshooting
Testing sequence/
Measure
Cause
Check connection
Establish good electrical
between SAFe and water
contact. Replace cable if
pressure sensor for poor
necessary.
contact, breaks and
damage.
Check water pressure
sensor.
Replace water pressure
sensor.
Check connecting cable
Rectify any short-
running to water pressure
circuits.
sensor.
Replace water pressure
Check water pressure
sensor.
sensor.
Check the connecting
Replace connecting
cable between the SAFe
cable if necessary.
and the return
Rectify contact problem
temperature sensor.
if necessary.
Check electrical
Replace temperature
connection of connecting
sensor is necessary.
cable to SAFe.
If temperature sensor
Check resistance levels of
resistances are correct
temperature sensor
but voltages incorrect,
against table
replace SAFe
Check voltage at
temperature sensor
terminals on SAFe against
table.
Check the connecting
Replace connecting
cable between the SAFe
cable if necessary.
and the return
Rectify contact problem
temperature sensor.
if necessary.
Check electrical
Replace temperature
connection of connecting
sensor is necessary.
cable to SAFe.
If temperature sensor
Check resistance levels of
resistances are correct
temperature sensor
but voltages incorrect,
against table
replace SAFe
Check voltage at
temperature sensor
terminals on SAFe against
table.
Faults have continually
Identify and eliminate
been simply reset and not
the cause of the problem
rectified.
causing the resets.
There is a fault on the
Replace BC10.
BC10 causing continual
Replace SAFe.
resets.
There is a malfunction on
the SAFe.
10
59