10
Troubleshooting
1)
Type
Display code Fault code
V
8Y
591
V
9Y
500
501
502
503
V
CY
566
V
CY
567
Table 23 Fault displays
1) V = interlocking; B = inhibiting; BC = operating code
58
Cause
Description
Faults when checking the
SAFe pressure switch
safety sequence.
has not tripped.
Internal SAFe relay fault.
Internal electronic fault
on SAFe.
Return temperature
The control unit receives
unrealistic values from
< 23 °F (< -5 °C) (circuit
the return sensor.
break)
Return temperature
The controller receives
unrealistic values from
> 266 °F (> 130 °C) (short-
the return temperature
circuit)
sensor.
Testing sequence/
Measure
Cause
Check whether the gas
Ensure a gas supply
supply pressure is
pressure of > 3 inches
> 3 inches W.C.
W.C.
Check setting of SAFe
pressure switch.
Adjust setting of SAFe
pressure switch to 3
inches w.c.
Check connector on gas
valve is properly seated.
Insert connector
properly.
Replace SAFe pressure
switch and wiring.
Replace SAFe.
Press Reset button and
If fault recurs after
wait to see if fault is
Reset, SAFe must be
eliminated.
replaced.
Check the connecting
Replace connecting
cable between the SAFe
cable if necessary.
and the return
Rectify contact problem
temperature sensor.
if necessary.
Check electrical
Replace temperature
connection of connecting
sensor is necessary.
cable to SAFe.
If temperature sensor
Check resistance levels of
resistances are correct
temperature sensor
but voltages incorrect,
against table.
replace SAFe.
Check voltage at
temperature sensor
terminals on SAFe against
table.
Check the connecting
Replace connecting
cable between the SAFe
cable if necessary.
and the return
Rectify contact problem
temperature sensor.
if necessary.
Check electrical
Replace temperature
connection of connecting
sensor is necessary.
cable to SAFe.
If temperature sensor
Check resistance levels of
resistances are correct
temperature sensor
but voltages incorrect,
against table.
replace SAFe.
Check voltage at
temperature sensor
terminals on SAFe against
table.
Logano plus GB312 – 6 720 806 273 (2013/01)