Buderus Logano plus GB312 Installation And Service Instructions Manual page 56

Gas condensing boiler
Table of Contents

Advertisement

10
Troubleshooting
1)
Type
Display code Fault code
K
6A
577
V
6L
561
Table 23 Fault displays
1) V = interlocking; B = inhibiting; BC = operating code
56
Cause
Description
No flame detected within
Ionization current
the safety period.
< 1.1 μA during safety
period.
5 power-up sequences
The burner control unit
(power supply
has switched off 5 times
disconnection during burner
during the burner start-
start-up).
up sequence.
Testing sequence/
Measure
Cause
Gas supply/dynamic
If pressure too low,
pressure too low.
inform gas company.
Install a gas pressure
The gas pressure
regulator that is
regulator is not
appropriate for the
appropriate for the
required gas volume. If
required gas volume.
necessary, notify the gas
supply company.
Install adequately
Inadequately sized gas
dimensioned gas piping
line cross-sections (min.
cross-section of the gas
connector pipe).
Bleeding the gas supply
Air in gas pipe.
pipe
Excessively high flue
Install properly
system backpressure
dimensioned and
through unfavorable
configured flue system.
layout (too many
diversions; cross-section
inadequate or too long;
horizontal sections too
long).
Clean or replace
Ignition/ionization
ignition/ionization
electrode dirty
electrode.
Establish good electrical
Check connecting cable
contact. Replace cable if
between SAFe and
necessary.
ionization electrode for
poor contact, breaks and
damage.
Check electrode gaps and
Align burner rod or
ignition/ionization
electrode. Replace
electrode for damage.
defective electrode.
Check connecting cable
between ignition
Establish good electrical
transformer and ignition
contact
electrode for poor
Replace cable if
contact (at electrode and
necessary.
transformer), breaks and
damage.
SAFe burner control unit
defective.
Replace SAFe.
Ignition transformer
defective (delayed or
Replace ignition
non-existent spark,
transformer.
"violent" start-up)
Check the 120V power
Reset burner control
supply to the control unit.
unit.
Rectify power supply
problem.
Logano plus GB312 – 6 720 806 273 (2013/01)