Buderus Logano plus GB312 Installation And Service Instructions Manual page 45

Gas condensing boiler
Table of Contents

Advertisement

Fig. 61 Wet cleaning the heat exchanger
Operations required on the heat exchanger when wet or dry
cleaning
▶ Use a hose to flush any dirt residues into the bucket.
▶ Clean the trap with water.
WARNING: Danger of fatal accident due to poisoning!
If the siphon is not filled with water, escaping flue gas
can place lives at risk.
▶ Fill the siphon with approx. 0.3 gallons of water.
▶ Reinstall the siphon (condensate trap).
Fig. 62 Cleaning the trap
Cleaning the burner
▶ Blow-clean the burner rods and manifold from inside and outside
with compressed air.
Logano plus GB312 – 6 720 806 273 (2013/01)
Fig. 63 Cleaning the burner
[1]
Burner rods
Servicing burner electrodes
Checking and adjusting electrode position
▶ Measure the distances between the electrodes as shown in Fig. 64
7 747 010 720-31.1RS
and adjust as necessary.
▶ Undo the screws on the electrode bracket. ( Fig. 65)
▶ Adjust the electrode bracket so that the electrodes are in the position
shown in Fig. 64.
▶ Tighten the screws on the electrode bracket.
7 747 010 720 70 1RS
Heating system inspection
A SW 4 mm Allen key can be used as gauge for checking
the gaps.
9
1
7 747 010 720-72.1RS
45