Conventional Automatic Detectors
NOTICE!
The cable length between the detector and the FAA-420-RI must not exceed 3 m when
connected by an unscreened cable.
Technical Specification FAA-420-RI
Operating voltage
Maximum current consumption
Display medium
Permissable wire gauge
Dimensions
Weight
5.7.2

External Detector Alarm Display MPA

Installation Notes
NOTICE!
The flat side of the prism (Y) must show in direction of the viewer.
Figure 5.2 Mounting the MPA
Connecting the MPA
The MPA will be connected to the Wago-clamps 1 to 4.
Connect: Put in the isolated wire (no braid) into the clamp.
Disconnect: Pull the wire out of the clamp by turning it back and forth.
You can connect up to four detectors onto each MPA.
Bosch Sicherheitssysteme GmbH
Installation directly onto wall or ceiling.
For surface cable feed break out the prepared inlets (X) at the housing wall.
For rear entry, conduit box mounting, feed the cable through the opening in the base
center.
1 2 3 4
Operation Guide
5 V DC to 30 V DC
20 mA
2 LEDs
0.6 mm to 2 mm
79 x 79 x 31 mm
approx. 45 g
60
55