Conventional Automatic Detectors
8
Specifications
Multisensor Detectors
Device Type
Detection principle
Special features
Operating voltage
Current consumption
Individual display
Alarm output
Indicator output
Response sensitivity (basic
data)
Max. monitoring range
Maximum installation height
Permissible air speed
Permissible operating temp.
Permissible relative humidity
Protection category according
to EN 60529
Color code
Dimensions without base
Dimensions with base
Housing material / color
Weight without packaging
Weight with packaging
Product ID
Bosch Sicherheitssysteme GmbH
FCP-OC320/FCP-OC320-R470
Combination of:
–
Scattered light measurement
–
Combustion gas measurement
–
Drift compensation of the optical
sensor and the gas sensor
Current increase (alarm resistor approx. 820 Ω or 470 Ω)
Open collector, connects through 0 V via 3.92 kΩ, max. 8 mA
–
Optical sensor:
< 0.15 dB/m (EN54-7)
–
Chemical sensor: ppm range
120 m
-10 °C . . . +50 °C
IP 43 with detector base with damp room seal
Blue ring
ABS / white, similar to RAL 9010, matte surface
approx. 80 g
approx. 125 g
F.01U.026.292/F.01U.026.867
Operation Guide
FCP-OT320/FCP-OT320-R470
–
Scattered light measurement
–
Measurement of absolute
temperature and temperature
increase
–
Drift compensation of the optical
sensor
8.5 V DC to 30 V DC
< 0.12 mA
LED red
–
Optical sensor:
< 0.15 dB/m (EN54-7)
–
Thermal sensor: Class A2R acc. to
EN 54-5
–
Thermal maximum unit:
> 54 °C
–
Thermal differential unit:
refer to table Page 30
2
(observe VdS guidelines)
16 m (observe VdS guidelines)
20 m/s
< 95% (non-condensing)
IP 40
circumference 99,5 x 52 mm
circumference 120 x 63,5 mm
F.01U.026.295/F.01U.026.862
Specifications | en
Combination of:
-20 °C . . . +50 °C
Black ring
approx. 75 g
approx. 115 g
F.01U.002.707 | 8.0 | 2011.10