Conventional Automatic Detectors
1

Product Description

NOTICE!
This Product Information describes the entire product range of the FCP-320/FCH-320
Conventional Automatic Fire Detectors.
The FCP-320/FCH-320 Conventional Automatic Fire Detectors works on the basis of the
conventional technology and combines standard detection methods such as scattered light
measurement and temperature measurement with gas measuring technology at the highest
configuration level.
This method uses state-of-the-art processing methods to evaluate the signals from the gas
sensor and scattered light sensor or thermal sensor.
Security against false alarms is thus increased significantly and detection time is reduced in
comparison with the fire detectors generally available on the market today.
Thanks to the higher information content of the multisensor detectors, the use of detectors is
possible in environments where pure smoke detectors cannot be used.
The detectors are available in the following configuration levels:
The detector's timeless and innovative design is a result of the cooperation between
engineers and designers. With this design it is possible to reconcile the contradictory goals of
a generous installation space and a small detector.
The placement of the individual display on the detector tip is the first externally visible
characteristic of the installation-friendly development concept. The stable and robust
detector base need no longer be aligned due to the position-independent position of the
individual display.
It is suitable for surface and flush mounting and includes separate mounting points for
dropped ceiling and concealed sockets. In addition, it fits all common bore patterns. For
surface mounting, the cable may be fed through on the side.
The integrated strain relief for interfloor cables prevents the removal of cables from the
terminal after installation. The terminals are easily accessible; a retainer for the end of line
resistor is integrated. Cable diameters of up to 2.5 mm
It can be equipped with a damp room seal so that all installation requirements can be covered
with one base.
The 320 Series detectors are available with either a 420 Ω alarm resistor or a 320 Ω alarm
resistor. The operating voltage range is 8.5 V DC to 32 V DC, which allows the detectors to be
used with almost every common conventional fire panel.
Bosch Sicherheitssysteme GmbH
FCP-OC320: Combined optical, gas-sensitive smoke detectors
FCP-OT320: Combined optical, thermal smoke detectors
FCP-O320: Optical smoke detectors
FCH-T320: Thermal detectors.
Operation Guide
Product Description | en
2
can be used.