Fas-Asd-Diag Diagnostic Software; External Detector Alarm Displays - Bosch FCS-320-TM Operation Manual

Fcs-320-tm aspirating smoke detector
Hide thumbs Also See for FCS-320-TM:
Table of Contents

Advertisement

20
en | Technical Specifications
2.5.5

FAS-ASD-DIAG Diagnostic Software

Figure 2.14 Diagnostic software for importing and reading out the device data
The FAS-ASD-DIAG Diagnostic Software enables the saved and current statuses of the
FCS-320-TM and error messages to be saved on a PC or laptop.
Data is transmitted to the diagnostic appliance via the infrared port of the aspirating smoke
detector. The USB cable provided is used to transmit the data from the diagnostic appliance
to the PC/laptop (see Figure 2.14).
Windows 2000 or Windows XP can be used as the operating system. For correct color display,
the monitor and graphics card must be able to display more than 256 colors.
Diagnostic messages remain saved in the FCS-320-TM for at least 3 days in order to be able to
evaluate even short, sporadically occurring errors (e.g. in case of changed operating
conditions).
Resetting the FCS-320-TM via the diagnostic software deletes all saved diagnostic messages.
The software also allows the deletion of error messages.
NOTICE!
The diagnostic software can be used to save in file format all stored and current diagnostics
data and any settings made via the fire panel programming software. To be able to compare
the data read out, save each file under a different file name.
2.5.6

External Detector Alarm Displays

A remote indicator must be connected if the aspirating smoke detector is not directly visible
or has been mounted in false ceilings or floors.
The external detector alarm display is installed in an obvious place in halls or entrances of the
building section or areas concerned.
Remote indicators can be actuated via the optional relay board. If FNS-320-TM-R variants with
fire source identification are used, the remote indicators are assigned to the various
monitoring ranges by the relay board and, in the event of a fire, identify the location of the
fire.
F.01U.130.928 | 1.0 | 2009.11
Operation Guide
FCS-320-TM Aspirating Smoke Detector
DIAG
Bosch Sicherheitssysteme GmbH

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fcs-320-tm-r

Table of Contents