Carrier AQUASNAP 30RB060-390 Controls, Start-Up, Operation, Service And Troubleshooting Instructions page 75

Air-cooled liquid chillers
Hide thumbs Also See for AQUASNAP 30RB060-390:
Table of Contents

Advertisement

T.REQ value to ON and press
mode is now active. Press the arrow keys to move to the appro-
priate item. To activate an item locate the item, press
and the display will show OFF. Press
flash. Use either arrow key to change the value to ON and
press
. The item should be active. To turn the item
ENTER
off, locate the item, press
ENTER
ON. The chiller must be enabled by turning the Enable/Off/
Remote Contact switch to Enable. Press
flash. Use either arrow key to change the value to OFF and
press
. The item should be inactive.
ENTER
To enter the Quick Test mode, the Enable/Off/Remote
Contact switch must be in the OFF position. Move the LED to
MODE
SUB-MODE
(Red LED)
SERVICE TEST
TEST
QUIC
. Manual Control
ENTER
ENTER
and OFF will
ENTER
and the display will show
and ON will
ENTER
Table 47 — Testing the Chilled Water Pump
KEYPAD
ITEM
ENTRY
ENTER
Q.REQ
ENTER
PASS WORD
ENTER
ENTER
ENTER
ENTER
ENTER
Q.REQ
ENTER
ENTER
ENTER
Q.REQ
ESCAPE
EXV.A
EXV.B
PMP.1
ENTER
ENTER
ENTER
ENTER
ENTER
the Service Test mode. Press
the
key until the display reads QUIC. Press
access Q.REQ. Press
Press
and OFF will flash. Enter the password if
ENTER
required. Use either arrow key to change the QUIC value to
ON and press
ENTER
low the same instructions for the Manual Control mode to acti-
vate a component.
Example — Test the chilled water pump (see Table 47).
Power must be applied to the unit. Enable/Off/Remote
Contact switch must be in the OFF position.
VALUE
DISPLAY
DESCRIPTION
EXPANSION
(Units)
Service Test Mode
Manual Sequence
0111
OFF
OFF
ON
Water Exchanger
Pump 1
OFF
OFF
ON
ON
ON
OFF
OFF
75
to access TEST. Use
ENTER
and the display will show OFF.
ENTER
. Quick Test mode is now active. Fol-
COMMENT
Password may be required
Each
will lock in the next
ENTER
digit. If 0111 is not the password,
use the arrow keys to change the
password digit and press
when correct.
Returns to the original field
OFF will flash
The Enable/Off/Remote Contact
switch must be in the OFF
position.
OFF will flash
Pump 1 will turn on.
ON will flash
Pump 1 will turn off.
to
ENTER
ENTER