Carrier AQUASNAP 30RB060-390 Controls, Start-Up, Operation, Service And Troubleshooting Instructions page 37

Air-cooled liquid chillers
Hide thumbs Also See for AQUASNAP 30RB060-390:
Table of Contents

Advertisement

MODE
KEYPAD ENTRY
CONFIGURATION
SETPOINTS
NOTE: Bold values indicate sub-mode level.
Table 28 — OAT Reset Configuration
DISPLAY
DISP
ENTER
UNIT
SERV
OPTN
RSET
Reset Cool and Heat Tmp
CRST
Cooling Reset Type
ENTER
0
No Reset
ENTER
0
No Reset
ENTER
/
1
Out Air Temp
1
ENTER
CRST
ESCAPE
ESCAPE
/
COOL
Cooling Setpoints
ENTER
CSP.1
Cooling Setpoint 1
ENTER
x 6
CRT.2
CRO1
OAT No Reset Temp
0
ENTER
0
ENTER
85.0
85.0
ENTER
CRO1
ESCAPE
CRO2
OAT Full Reset Temp
0
ENTER
0
ENTER
55.0
55.0
ENTER
CRO2
ESCAPE
CRS1
CRS2
DGRC
Degrees Cool Reset
0
ENTER
0
ENTER
15.0
15.0
ENTER
DGRC
ESCAPE
ITEM EXPANSION
Flashing to indicate Edit mode. May require Password
Use up or down arrows to change value to 1.
Accepts the change.
At mode level
Change to Setpoints Mode
Outdoor Temperature where no temperature reset is
required.
Value of CRO1
Flashing to indicate Edit mode
Value of No Temperature Reset, 85 from the example.
Accepts the change.
Outdoor Temperature where full temperature reset,
DGRC is required.
Value of CRO2.
Flashing to indicate Edit mode
Value of full Temperature Reset, 55 from the example.
Accepts the change.
Amount of temperature reset required.
Value of DGRC
Flashing to indicate Edit mode
Amount of Temperature Reset required, 15 from the
example.
Accepts the change.
37