Carrier AquaEdge 23XRV Controls Operation And Troubleshooting

Carrier AquaEdge 23XRV Controls Operation And Troubleshooting

Variable speed high-efficiency screw liquid chillers with pic6 controls

Advertisement

Quick Links

Controls Operation and Troubleshooting
CONTENTS
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . 1
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Abbreviations Used in This Manual . . . . . . . . . . . . . . 2
HARDWARE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Main PIC6 Control HMI. . . . . . . . . . . . . . . . . . . . . . . . . 2
SIOB (Starfire Input/Output Board) . . . . . . . . . . . . . . 2
IOB (Input/Output Board) . . . . . . . . . . . . . . . . . . . . . . 3
Communication Cables . . . . . . . . . . . . . . . . . . . . . . . 11
Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Controls Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
USER INTERFACE . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Web Connection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
General Interface Features . . . . . . . . . . . . . . . . . . . . 12
CONTROL OPERATION . . . . . . . . . . . . . . . . . . . . . . . 16
Start-Stop Control . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Compressor Run Status . . . . . . . . . . . . . . . . . . . . . . 17
Chiller Start-Up Sequence. . . . . . . . . . . . . . . . . . . . . 17
Chiller Shutdown Sequence . . . . . . . . . . . . . . . . . . . 18
Control Points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Displaying Data Trends . . . . . . . . . . . . . . . . . . . . . . . 24
Hydraulic Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Alarm/Alert Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Displaying Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Resetting Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
CONTROLLER SETTINGS . . . . . . . . . . . . . . . . . . . . . 34
Unit IP Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
DNS Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
CCN Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
COMMUNICATION PROBLEMS . . . . . . . . . . . . . . . . 35
Hardware Problems . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Web Interface Problems . . . . . . . . . . . . . . . . . . . . . . 35
Ethernet/IP Connection Problems . . . . . . . . . . . . . . 36
STRUCTURE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
STATUS INDICATORS . . . . . . . . . . . . . . . . . . . . . 59

SAFETY CONSIDERATIONS

Installing, starting up, and servicing this equipment can be haz-
ardous due to system pressures, electrical components, and
equipment location (roof, elevated structures, etc.). Only trained,
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53230018-01
Page
Printed in U.S.A.
Form 23XRV-1T
23XRV Variable Speed
High-Efficiency Screw Liquid Chillers
qualified installers and service mechanics should install, start up,
and service this equipment. When working on this equipment,
observe precautions in the literature, and on tags, stickers, and
labels attached to the equipment, and any other safety precau-
tions that apply. Follow all safety codes. Wear safety glasses and
work gloves. Use care in handling, rigging, and setting this
equipment, and in handling all electrical components.
ELECTRICAL SHOCK HAZARD
Failure to follow this warning will result in personal injury or
death.
Before performing service or maintenance operations on unit,
turn off main power switch to unit and install lock(s) and
lockout tag(s). Ensure electrical service to rooftop unit agrees
with voltage and amperage listed on the unit rating plate. Unit
may have more than one power switch.
Electrical currents cause components to get hot either tempo-
rarily or permanently and may cause burns. Handle power
cable, electrical cables and conduits, terminal box covers,
and motor frames with great care.
This unit uses a microprocessor control system. Do not short
or jumper between terminations on circuit boards or modules;
control or board failure may result.
Be aware of electrostatic discharge (static electricity) when
handling or making contact with circuit boards or module con-
nections. Always touch a chassis (grounded) part to dissipate
body electrostatic charge before working inside control center.
Use extreme care when handling tools near boards and when
connecting or disconnecting terminal plugs. Circuit boards can
easily be damaged. Always hold boards by the edges and
avoid touching components and connections.
This equipment uses, and can radiate, radio frequency energy.
If not installed and used in accordance with the instruction
manual, it may cause interference to radio communications.
The PIC6 control boards have been tested and found to com-
ply with the limits for a Class A computing device pursuant to
International Standard in North America EN 61000-2/3 which
are designed to provide reasonable protection against such in-
terference when operated in a commercial environment. Oper-
ation of this equipment in a residential area is likely to cause
interference, in which case the user, at his own expense, will
be required to take whatever measures may be required to cor-
rect the interference.
Always store and transport replacement or defective boards in
anti-static shipping bag.
Pg 1
AquaEdge
with PIC6 Controls
DANGER
WARNING
CAUTION
6-22
Replaces: New
®

Advertisement

Table of Contents
loading

Summary of Contents for Carrier AquaEdge 23XRV

  • Page 1: Table Of Contents

    AquaEdge ® 23XRV Variable Speed High-Efficiency Screw Liquid Chillers with PIC6 Controls Controls Operation and Troubleshooting qualified installers and service mechanics should install, start up, CONTENTS and service this equipment. When working on this equipment, Page observe precautions in the literature, and on tags, stickers, and labels attached to the equipment, and any other safety precau- SAFETY CONSIDERATIONS .
  • Page 2: General

    The following abbreviations are used in this manual: J5 — USB CONNECTOR J6 — LEN CONNECTOR — American Wire Gauge — Carrier Comfort Network ® J7 — CCN CONNECTOR CCN mode — Operating mode: CCN J8 — RS485, BACnet MS/TP OR Modbus RTU DHCP —...
  • Page 3: Iob (Input/Output Board)

    23XRV IOB COMPONENTS AND WIRING IOB (Input/Output Board) The IOB is supplied from a 24 VAC supply reference to earth The components listed in Tables 1-3 are available at the user’s ground. terminal block on the IOB. Many are routed to the 7TB terminal block located on the left side of the low voltage VFD section.
  • Page 4 Table 3 — 23XRV IOB2 Connections a,b,c DESCRIPTION CHANNEL TERMINAL TYPE OPTIONAL Entering Evaporator Water Pressure J16-3,7 Signal, J11-1 Optional Field Connections 7TB-36 (reference), 7TB-37 (Vout), 7TB-64 (Vin) Leaving Evaporator Water Pressure J16-4,8 Signal, J11-2 Optional Field Connections 7TB-38 (reference), 7TB-39 (Vout), 7TB-65 (Vin) Entering Condenser Water Pressure J15-6,12 Signal, J11-3 Optional Field Connections 7TB-41 (reference) 7TB-40 (Vout), 7TB-66 (Vin)
  • Page 5 NOTE: Carrier recommends using a relay with a contact rating of 10 amp sealed RMS or greater with 24VAC coil. Fig. 4 — SIOB...
  • Page 6 FROM 2000767952, SHEET 3 Fig. 5 — 1IOB...
  • Page 7 Fig. 6 — 2IOB...
  • Page 8 Fig. 7 — Control Wiring...
  • Page 9 Fig. 8 — 23XRV Controls Schematic...
  • Page 10 CN1A - Red Modem Power CN1B - Black Supply 24V Control Transformer Ethernet 7TB (includes Switch field wiring) Modem Oil Heater (Secondary) Vaporizer Heater Oil Heater (Primary) Oil Pump HGBP Chilled Water Pump Pilot Relay Condenser Water Pump Pilot Relay VFD Run Permissive Controls Power Circuit Breaker...
  • Page 11: Communication Cables

    IOBs/SIOB. See Table 4. EVAPORATOR/CONDENSER WATER PUMP Table 4 — Pressure Transducers The controller regulates the evaporator/condenser water pump. Note that Carrier requires full or parallel pump control since Carri- PRESSURE er controls utilize the pumps for freeze protection and high pres- PURPOSE TRANSDUCER sure control.
  • Page 12: General Interface Features

    SCREENS General Interface Features The Human Machine Interface includes the following screens: ICONS • Home screen, which displays the main parameters Table 6 shows general interface icons. • Menu screens for navigation Table 6 — Interface Icons • Data/configuration screens, which list the parameters by type •...
  • Page 13 Messages When a start-up is initiated, a status screen displays the progress of the start-up sequence. See Fig. 13 and 14. The Set Point screen, On/Off screen, User Login screen, and Main Menu screens described in the next sections may display status messages at the bottom of the screen.
  • Page 14 Factory access (located under Service Login icon) allows access to critical factory configuration settings and only authorized users will have access to these menus using Carrier Smart Service. From the Home screen, touching the Globe icon displays the Language and Units Selection screen. See Fig. 16.
  • Page 15 Fig. 23 — System Overview (Home) Screen Fig. 21 — General Configuration Screen After changing a value, press Return. The Save and Cancel icons are displayed. Press the Save icon to save the changed value. In the General Configuration menu the ramp loading per time can be limited based on ^F, amps, or kW.
  • Page 16: Control Operation

    Fig. 31 — Economizer Status (TP Only) Fig. 27 — Compressor Status CONTROL OPERATION Start-Stop Control This function controls the chiller START-STOP command. The selectable control modes are Local or AutoStart. See Unit Start/ Stop Screen (Basic log-in). Specific control sources are valid to start or stop the chiller for each control mode.
  • Page 17: Compressor Run Status

    either Modbus, BACnet, or CCN, and must be enabled on the Chiller Start-Up Sequence Configure Startup Options screen. PRE-START CHECK Compressor Run Status Once start-up begins, the controller performs a series of pre-start Compressor run status is shown at the top of the system over- tests to verify that all pre-start alerts and safeties are within lim- view (home) screen.
  • Page 18: Chiller Shutdown Sequence

    START-UP all running compressors. Otherwise, the system will ramp com- pressor down. After a successful pre-start check, the chilled water pump relay is energized. Condenser pump relay is turned on 5 seconds after the OIL PUMP AND EXV (AS APPLICABLE) STOPPING evaporator pump relay.
  • Page 19 can be monitored for increasing load. The recycle control uses CAPACITY CONTROL Recycle Startup Offset to check when the compressor should From the compressor relay closed point to the end of ramp load- be restarted. In cooling mode, the compressor will restart when ing, the VFD TARGET SPEED is the configured Motor Start the leaving chilled water temperature (or entering chilled water Speed.
  • Page 20 Unit Status is Timeout. WATER PUMPS CONTROL (FREEZE PREVENTION) Carrier must have direct or parallel control of the chiller water pumps. Pump control connection must be either hardwire of con- trolled via BMS commands that originates from chiller controller.
  • Page 21 Alarm 515 for evaporator freeze protection will be initiated when the sensed water temperature is below the Fluid Freeze Point + 1°F (0.55°C). Default Fluid Freeze Point = 34°F (1.1°C). Alarm 531 for low refrigerant temp is activated when the calcu- lated evaporator suction temperature or measured liquid tem- perature is less than the Fluid Freeze Point + 1°F (0.55°C).
  • Page 22 Any Alarm (not Alert) will trigger a Black Box recording and data will be overwritten once 20 files are reached. The black box file can be uploaded with the Carrier Service Tool or the USB Log Export feature (Main MenuSystem Config MenuUSB Log Export).
  • Page 23 Fig. 47 — USB Log Export Menu Fig. 50 — Transducer Calibration Menu Black box data can be triggered manually which is useful for trou- Each transducer is supplied with 5 vdc from the 1IOB and bleshooting. Login level is Service or higher and the black box SIOB.
  • Page 24: Displaying Data Trends

    Fig. 55 — Controller ID Screen Fig. 53 — Temperature Input Menu, Page 2 Displaying Data Trends The PIC6 control system offers the ability to configure and display Place the temperature sensor in a 32°F (0°C) water solution color-coded system trends. Select Main Menu  Trending. or other known temperature in range where the sensor is used.
  • Page 25: Hydraulic Option

    Hydraulic Option DIAGNOSTICS AND TROUBLESHOOTING The 23XR unit can be equipped with two normally open flow The 23XRV PIC6 control system has many fault tracing aid func- switches; one for the evaporator and the other for the condenser. tions. The local interface and its various menus give access to all The evaporator/condenser water flow will indicate the flow sta- unit operating conditions.
  • Page 26: Alarm/Alert Codes

    Alarm/Alert Codes Displaying Alarms Table 10 lists PIC6 alert codes. Table 11 lists PIC6 alarm codes. The alarm icon on the interface (see the section Icons on Alerts do not cause machine shutdown and are typically automati- page 12) indicates unit status as follows: cally reset when the situation returns to normal, while alarms typi- •...
  • Page 27 Table 10 — PIC6 Alert Codes (cont) HITS TO HITS TO CODE RESET TYPE RESPONSE MESSAGE TRIP CONDITION TROUBLESHOOTING ACTIVATE RESET Verify continuity to SIOB. Verify voltage and ohm reading across Remote reset temperature ALT-011 Sensor Alert - Remote sensor. Replace sensor if ohm ALT011 AUTOMATIC Notify...
  • Page 28 Table 10 — PIC6 Alert Codes (cont) HITS TO HITS TO CODE RESET TYPE RESPONSE MESSAGE TRIP CONDITION TROUBLESHOOTING ACTIVATE RESET ALT-417 Prestart Alert - Invalid Compressor envelope selection ALT417 AUTOMATIC Prevent Circuit Startup Reload software Compressor Envelope - Cir A is invalid VFD or STARTER line voltage is Check actual line voltage and...
  • Page 29 Table 10 — PIC6 Alert Codes (cont) HITS TO HITS TO CODE RESET TYPE RESPONSE MESSAGE TRIP CONDITION TROUBLESHOOTING ACTIVATE RESET System maintains CRT(TEMP_CND_ST_A) at or above the Condenser Freeze Point subject to ALL of the following: • Unit is not in pumpdown (GENUNIT_STATUS != 11) Check condenser pressure transducer for accuracy.
  • Page 30 Table 11 — PIC6 Alarm Codes HITS TO HITS TO CODE RESET TYPE RESPONSE MESSAGE TRIP CONDITION TROUBLESHOOTING ACTIVATE RESET Verify continuity to appropriate board. Verify voltage and ohm reading Prevent Unit Startup or ALM-002 Sensor Fault - Entering chilled water temperature ALM002 AUTOMATIC across sensor.
  • Page 31 Table 11 — PIC6 Alarm Codes (cont) HITS TO HITS TO CODE RESET TYPE RESPONSE MESSAGE TRIP CONDITION TROUBLESHOOTING ACTIVATE RESET Verify comm wiring. Verify correct terminations at VFD. Verify ALM-102 VFD Fault - Communication between main Prevent Circuit Startup grounding to comm wire leg.
  • Page 32 Table 11 — PIC6 Alarm Codes (cont) HITS TO HITS TO CODE RESET TYPE RESPONSE MESSAGE TRIP CONDITION TROUBLESHOOTING ACTIVATE RESET Compressor operation is allowed AND (HYDRCFG_cflo_vt) has expired AND IF (HYDRCFG_condfdtp) = 1 and (INPUTS_COND_FSW) is ALM-506 Protective Verify setting in Hydronics Prevent Unit Startup or FALSE ALM506...
  • Page 33 Table 11 — PIC6 Alarm Codes (cont) HITS TO HITS TO CODE RESET TYPE RESPONSE MESSAGE TRIP CONDITION TROUBLESHOOTING ACTIVATE RESET Chiller is running AND compressor discharge temperature sensor is in range AND compressor discharge temp (TEMP_DGT_A) > 140°F. ALM-523 Protective System maintains DT at or below Prevent Circuit Startup ALM523...
  • Page 34: Controller Settings

    CONTROLLER SETTINGS The controller settings are accessible through the System Config Menu (Service password access required). See Fig. 61 and 62. Fig. 63 — Ethernet Configuration Enter the new address, Subnet Mask, and Default Gateway and validate it by pressing OK and Save. Return to the Network screen and enter the subnet mask and default gateway using the same method.
  • Page 35: Building Automation System Communication

    Protocol). Establishing communication between a site building automation system and the PIC6 controller is not part of the standard Carrier startup process. If it is necessary to support chiller control integra- tion with the site building automation system, it will require a re- quest from the Carrier Service Office/Distributor for a control technician to complete this task and additional charges will apply.
  • Page 36: Ethernet/Ip Connection Problems

    Table 12 — Hardware Problems SYMPTOMS POSSIBLE CAUSES CHECKS SOLUTIONS The unit does not respond to the instruc- Problem at the RS485 converter level of Check the CCN cable connections. The Replace the RS485 connector. tions sent by the supervision PC on the the PC or connection problem on the pri- unit CCN address is 0.1 and the com- CCN bus.
  • Page 37 In the example shown in Fig. 72, the PC receives four negative re- If a proxy server is used, add the unit IP address to the exceptions sponses (request timed out). list of the proxy server (advanced proxy configuration). See Fig.
  • Page 38 JAVA APPLICATION CONFIGURATION Open the Internet configuration window of the PC and double- click the Java application icon. If Java is not installed, a free download is available at http://www.java.com. If Java has already been installed, check if it is used by other appli- cations.
  • Page 39: Appendix A - Pic6 Screen And Table Structure

    APPENDIX A — PIC6 SCREEN AND TABLE STRUCTURE CHOOSE OPERATING MODE HOME MAIN MENU LOG IN / LOG OUT CONFIRM STOP ALARM MENU Fig. A — Screen Structure, Basic Level (All) Access (No Password Required) HOME MAIN MENU LOG IN / LOG OUT CHOOSE OPERATING MODE CONFIRM STOP ALARM MENU...
  • Page 40 APPENDIX A — PIC 6 SCREEN AND TABLE STRUCTURE (cont) HOME MAIN MENU LOG IN / LOG OUT CHOOSE OPERATING MODE CONFIRM STOP ALARM MENU Fig. C — Screen Structure, Service Level Access (Service Password 1234 or 3333 Required) HOME MAIN MENU LOG IN / LOG OUT CHOOSE OPERATING MODE...
  • Page 41 APPENDIX A — PIC 6 SCREEN AND TABLE STRUCTURE (cont) Main Menu Description ICON DISPLAYED TEXT ACCESS ASSOCIATED TABLE Inputs Menu Inputs Menu Outputs OUTPUTS Status Status Runtime RUNTIME Control Algo Menu User Control Algorithm Menu Setpoint SETPOINT Configuration Menu Service, Factory Configuration Menu System Configuration Menu...
  • Page 42 APPENDIX A — PIC6 SCREEN AND TABLE STRUCTURE (cont) NOTE: The PIC6 controls platform is utilized across multiple product lines. In this appendix, all PIC6 software lines are shown, as configured for 23XR software. Not all lines may be applicable for the 23XR product. Temperature CCN TABLE NAME: TEMP PIC6 PATH: Main Menu ...
  • Page 43 APPENDIX A — PIC6 SCREEN AND TABLE STRUCTURE (cont) Outputs CCN TABLE NAME: OUTPUTS PIC6 PATH: Main Menu  Outputs LINE PIC6 DESCRIPTION CCN NAME RANGE DEFAULT VALUE UNIT READ/WRITE Alert Relay OFF_ON — Alarm Relay OFF_ON — Running Relay OFF_ON —...
  • Page 44 APPENDIX A — PIC6 SCREEN AND TABLE STRUCTURE (cont) Drive A Status CCN TABLE NAME: DRVA1STS PIC6 PATH: Main Menu  Status Menu  Drive A Status LINE PIC6 DESCRIPTION CCN NAME RANGE DEFAULT VALUE UNIT READ/WRITE VFD Coms Status COMS 0 to 2 —...
  • Page 45 APPENDIX A — PIC6 SCREEN AND TABLE STRUCTURE (cont) Protocol Commands CCN TABLE NAME: PROTOCOL PIC6 PATH: Main MenuStatus MenuProtocol Commands LINE PIC6 DESCRIPTION CCN NAME RANGE DEFAULT VALUE UNIT READ/WRITE CCN Occupy CCNOCC OFF_ON — CCN Demand Limit CCNDEML 40 to 100 CCN Estop CCNESTOP...
  • Page 46 APPENDIX A — PIC6 SCREEN AND TABLE STRUCTURE (cont) Control Algo CCN TABLE NAME: CONTROL PIC6 PATH: Main Menu  Control Algo Menu MENU NAME MENU TEXT DESCRIPTION ACCESS MENU ICONS CIRACTL Circuit A Control Menu USER CAPCTL Capacity Control USER EPMPCTL Evap Pump Control...
  • Page 47 APPENDIX A — PIC6 SCREEN AND TABLE STRUCTURE (cont) Reset Configuration CCN TABLE NAME: RESETCFG PIC6 PATH: Main Menu  Configuration Menu  Reset Config LINE PIC6 DESCRIPTION CCN NAME RANGE DEFAULT VALUE UNIT READ/WRITE Temp Reset Type res_sel 0 to 3 —...
  • Page 48 APPENDIX A — PIC6 SCREEN AND TABLE STRUCTURE (cont) Comp A Config CCN TABLE NAME: CMPA1CFG PIC6 PATH: Main Menu  Configuration Menu  Circuit A Config Menu  Comp A Config LINE PIC6 DESCRIPTION CCN NAME RANGE DEFAULT VALUE UNIT READ/WRITE Cmp A LowSatSuctOffset...
  • Page 49 APPENDIX A — PIC6 SCREEN AND TABLE STRUCTURE (cont) Drive A Configuration CCN TABLE NAME: DRVA1CFG PIC6 PATH: Main Menu  Configuration Menu  Circuit A Config Menu  Drive A Config LINE PIC6 DESCRIPTION CCN NAME RANGE DEFAULT VALUE UNIT READ/WRITE 0 to 0...
  • Page 50 APPENDIX A — PIC6 SCREEN AND TABLE STRUCTURE (cont) Update Runtime CCN TABLE NAME: UPDRUNT PIC6 PATH: Main Menu  Configuration Menu  Update Run Time Limits Configuration CCN TABLE NAME: LIMITCFG PIC6 PATH: Main Menu  Configuration Menu  Limits Config Head Pressure Config CCN TABLE NAME: HDPRCFG PIC6 PATH: Main Menu ...
  • Page 51 APPENDIX A — PIC6 SCREEN AND TABLE STRUCTURE (cont) Date/Time Config Menu CCN TABLE NAME: TIMECFG PIC6 PATH: Main Menu  System Configuration Menu  Date/Time Configuration Menu MENU NAME MENU TEXT DESCRIPTION ACCESS MENU ICONS USER Date/Time Configuration DATETIME USER NTP Time Sync NPCTIME...
  • Page 52 APPENDIX A — PIC6 SCREEN AND TABLE STRUCTURE (cont) Network Configuration - Eth1 Configuration CCN TABLE NAME: ETH1CONF PIC6 PATH: Main Menu  Systems Configuration Menu  Network  Eth1 Config Network Configuration - DNS Configuration CCN TABLE NAME: DNS PIC6 PATH: Main Menu ...
  • Page 53 APPENDIX A — PIC6 SCREEN AND TABLE STRUCTURE (cont) Network Configuration - IOT Cloud Diagnostics CCN TABLE NAME: IOTCLDDG PIC6 PATH: Main Menu  Systems Configuration Menu  Network  IOT Cloud Diagnostics Alarm Email Config CCN TABLE NAME: EMAILCFG PIC6 PATH: Main Menu ...
  • Page 54 APPENDIX A — PIC6 SCREEN AND TABLE STRUCTURE (cont) Controller ID CCN TABLE NAME: CTRLID PIC6 PATH: Main Menu  Systems Configuration Menu  Controller ID System Information CCN TABLE NAME: SYSINFO PIC6 PATH: Main Menu  Systems Configuration Menu  System Information CCN Protocol Menu - CCN Configuration CCN TABLE NAME: CNN PIC6 PATH: Main Menu ...
  • Page 55 APPENDIX A — PIC6 SCREEN AND TABLE STRUCTURE (cont) BACnet Protocol Menu CCN TABLE NAME: BACNET PIC6 PATH: Main Menu  System Configuration Menu  BACnet Protocol Menu  BACnet Config BACnet IP BACnet MS/TP Modbus Protocol Menu CCN TABLE NAME: MODBUS PIC6 PATH: Main Menu ...
  • Page 56 APPENDIX A — PIC6 SCREEN AND TABLE STRUCTURE (cont) USB Log Export CCN TABLE NAME: USBEXPRT PIC6 PATH: Main Menu  Systems Configuration Menu  USB Log Export Local Schedule CCN TABLE NAME: LOCALOCC PIC6 PATH: Main Menu  Schedule Menu  Local Schedule Holiday Schedule CCN TABLE NAME: HOLIDAY PIC6 PATH: Main Menu ...
  • Page 57 APPENDIX A — PIC6 SCREEN AND TABLE STRUCTURE (cont) Trending CCN TABLE NAME: TRENDING PIC6 PATH: Main Menu  Trending Quick Test A CCN TABLE NAME: QCKTESTA PIC6 PATH: Main Menu  Quick Test Menu  Quick Test A LINE PIC6 DESCRIPTION CCN NAME RANGE...
  • Page 58 APPENDIX A — PIC6 SCREEN AND TABLE STRUCTURE (cont) Thermistor Calibration CCN TABLE NAME: THRMCALB PIC6 PATH: Main Menu  Quick Test Menu  Thermistor Calibration Transducer Calibration CCN TABLE NAME: TRNSCALB PIC6 PATH: Main Menu  Quick Test Menu  Transducer Calibration Alarms Menu Description ICON DISPLAYED TEXT...
  • Page 59: Appendix B - Control Panel Pcb Board Status Indicators

    APPENDIX B — CONTROL PANEL PCB BOARD STATUS INDICATORS INPUT/OUTPUT BOARD (IOB) SIOB BOARD All IOB boards have LED indicators that show control board and For diagnostic purposes the SIOB can visually be checked as communication status. follows: A red LED on each control module operates in the following •...
  • Page 60: Appendix C - Network Configuration

    APPENDIX C — NETWORK CONFIGURATION BACnet Points List OBJECT NAME TYPE INSTANCE OPTION COVINC PV ACCESS DESCRIPTION ALARMRST_alarm_1 Type 6 Jbus Current Alarm 1 ALARMRST_alarm_2 Type 6 Jbus Current Alarm 2 ALARMRST_alarm_3 Type 6 Jbus Current Alarm 3 ALARMRST_alarm_4 Type 6 Jbus Current Alarm 4 ALARMRST_alarm_5 Type 6...
  • Page 61 APPENDIX C — NETWORK CONFIGURATION (cont) BACnet Points List (cont) OBJECT NAME TYPE INSTANCE OPTION COVINC PV ACCESS DESCRIPTION CMPA1CTL_isRd2St Type 4 CmpA Ready to Stop CMPA1CTL_isStart Type 4 CmpA Started CMPA1CTL_isStop Type 4 CmpA Stopped CMPA1CTL_iTS Type 6 CmpA Inverter Temp Setpt CMPA1CTL_mTS Type 6 CmpA Motor Temp Setpt...
  • Page 62 APPENDIX C — NETWORK CONFIGURATION (cont) BACnet Points List (cont) OBJECT NAME TYPE INSTANCE OPTION COVINC PV ACCESS DESCRIPTION ECOACTL_dTStpt Type 6 Econ Disch Temp Setpoint ECOACTL_dWd Type 6 Diag Word ECOACTL_fWd Type 6 Fault Word ECOACTL_isEnable Type 4 Enable ECOACTL_isNom Type 4 Nominal...
  • Page 63 APPENDIX C — NETWORK CONFIGURATION (cont) BACnet Points List (cont) OBJECT NAME TYPE INSTANCE OPTION COVINC PV ACCESS DESCRIPTION FACTORY_exv_opt Type 5 EXV Control Type FACTORY_hgbp_opt Type 4 HGBP Control Option FACTORY_oilassy Type 6 Oil Assembly Option FACTORY_refrig Type 5 Refrigerant Type FACTORY_tons Type 6...
  • Page 64 APPENDIX C — NETWORK CONFIGURATION (cont) BACnet Points List (cont) OBJECT NAME TYPE INSTANCE OPTION COVINC PV ACCESS DESCRIPTION INPUTS_HPS_A Type 4 High Pressure Switch A INPUTS_HPS_B Type 4 High Pressure Switch B INPUTS_ICE_CON Type 4 Ice Build Contact INPUTS_ICE_SW Type 4 Ice Done Storage Switch INPUTS_OIL_L_A...
  • Page 65 APPENDIX C — NETWORK CONFIGURATION (cont) BACnet Points List (cont) OBJECT NAME TYPE INSTANCE OPTION COVINC PV ACCESS DESCRIPTION OUTPUTS_HDPV_OUT Type 6 Head Pres Output OUTPUTS_HGBP_A Type 4 HGBP Soleniod A OUTPUTS_HGBP_B Type 4 HGBP Soleniod B OUTPUTS_MTR_CL_A Type 4 Motor Cooling Solenoid A OUTPUTS_MTR_CL_B Type 4...
  • Page 66 APPENDIX C — NETWORK CONFIGURATION (cont) BACnet Points List (cont) OBJECT NAME TYPE INSTANCE OPTION COVINC PV ACCESS DESCRIPTION RUNTIME_hr_comp_b Type 6 Compressor B Hours RUNTIME_hr_cpmp1 Type 6 Cond Pump 1 Hours RUNTIME_hr_epmp1 Type 6 Evap Pump 1 Hours RUNTIME_hr_mach Type 6 Machine Operating Hours RUNTIME_hr_oilpa...
  • Page 67 APPENDIX C — NETWORK CONFIGURATION (cont) BACnet Points List (cont) OBJECT NAME TYPE INSTANCE OPTION COVINC PV ACCESS DESCRIPTION SLVA1CTL_fWd Type 6 SVA Fault Word SLVA1CTL_isEnable Type 4 SVA Enable SLVA1CTL_isNom Type 4 SVA Nominal SLVA1CTL_isRd2Go Type 4 SVA Ready to Start SLVA1CTL_isRd2St Type 4 SVA Ready to Stop...
  • Page 68 APPENDIX C — NETWORK CONFIGURATION (cont) BACnet Points List (cont) OBJECT NAME TYPE INSTANCE OPTION COVINC PV ACCESS DESCRIPTION STRTSTS_volt_unb Type 4 Voltage Imbalance TEMP_CND_ST_A Type 6 Cond Sat Temp A TEMP_CND_ST_B Type 6 Cond Sat Temp B TEMP_CNDAPP_A Type 6 Condenser Approach A TEMP_CNDAPP_B Type 6...
  • Page 69: Appendix D - Modbus Configuration

    APPENDIX D — MODBUS CONFIGURATION ADDRESS DISPLAY VALUE REG. N° PARAMETER DESCRIPTION MODE TYPE UNIT COMMENT HEXADEC. DEC. MIN. MAX. DEFAULT (16BITS) MV:0=Temp, 0x0001 GENCONF_rampsel Ramp Loading Type UINT 1=Current, 2=KW 0x0002 GENCONF_ramp_en Enable Ramp Loading UINT °F 0x0003 GENCONF_rrate_t Ramp Rate (per Min) FLOAT °C...
  • Page 70 APPENDIX D — MODBUS CONFIGURATION (cont) ADDRESS DISPLAY VALUE REG. N° PARAMETER DESCRIPTION MODE TYPE UNIT COMMENT HEXADEC. DEC. MIN. MAX. DEFAULT (16BITS) MV: 0=OFF, 1=DELAY, 2=READY, 3=RECYCLE, 4=PRESTART, 5=STARTUP, 6=AUTORESTART, 7=RUNNING, 8=DEMAND, 0x0028 GENUNIT_STATUS Unit Status UINT 9=RAMPING, 10=STOPPING, 11=TRIPOUT, 12=SERV_TEST, 13=PUMPDOWN,...
  • Page 71 APPENDIX D — MODBUS CONFIGURATION (cont) ADDRESS DISPLAY VALUE REG. N° PARAMETER DESCRIPTION MODE TYPE UNIT COMMENT HEXADEC. DEC. MIN. MAX. DEFAULT (16BITS) 0x004B TEMP_DSH_A Discharge Superheat A FLOAT 0x004C TEMP_CNDAPP_A Condenser Approach A FLOAT °F 0x004D TEMP_MTRW_A Motor Winding Temp A FLOAT °C –17.78...
  • Page 72 APPENDIX D — MODBUS CONFIGURATION (cont) ADDRESS DISPLAY VALUE REG. N° PARAMETER DESCRIPTION MODE TYPE UNIT COMMENT HEXADEC. DEC. MIN. MAX. DEFAULT (16BITS) psig 0x006C PRESSURE_EVAP_LWP Leaving Evap Water Pres FLOAT psig 0x006D PRESSURE_EVAP_WDP Evap Water Delta P FLOAT psig 0x006E PRESSURE_COND_EWP Entering Cond Water Pres FLOAT...
  • Page 73 APPENDIX D — MODBUS CONFIGURATION (cont) ADDRESS DISPLAY VALUE REG. N° PARAMETER DESCRIPTION MODE TYPE UNIT COMMENT HEXADEC. DEC. MIN. MAX. DEFAULT (16BITS) 0x0094 OUTPUTS_CAPOUT_A Analog Capacity Output A FLOAT 0x0095 OUTPUTS_ECOEXV_A Economizer EXV A FLOAT 0x0096 OUTPUTS_EXV_A Main EXV A FLOAT 0x0097 OUTPUTS_HGBP_A...
  • Page 74 APPENDIX D — MODBUS CONFIGURATION (cont) ADDRESS DISPLAY VALUE REG. N° PARAMETER DESCRIPTION MODE TYPE UNIT COMMENT HEXADEC. DEC. MIN. MAX. DEFAULT (16BITS) 0x00D7 STRTSTS_sum2ht_h I2T Sum Heat Phase 2 FLOAT 0x00D8 STRTSTS_sum3ht_h I2T Sum Heat Phase 3 FLOAT 0x00D9 STRTSTS_KW Motor KW FLOAT...
  • Page 75 APPENDIX D — MODBUS CONFIGURATION (cont) ADDRESS DISPLAY VALUE REG. N° PARAMETER DESCRIPTION MODE TYPE UNIT COMMENT HEXADEC. DEC. MIN. MAX. DEFAULT (16BITS) 0x0118 CMPA1CTL_aSSTMx CmpA AbsSuctSatTMax FLOAT 0x0119 CMPA1CTL_cAN CmpA Act Nom Capacity FLOAT 0x011A CMPA1CTL_cANp CmpA Act Nom Cap Pct FLOAT 0x011B CMPA1CTL_cASp...
  • Page 76 APPENDIX D — MODBUS CONFIGURATION (cont) ADDRESS DISPLAY VALUE REG. N° PARAMETER DESCRIPTION MODE TYPE UNIT COMMENT HEXADEC. DEC. MIN. MAX. DEFAULT (16BITS) 0x015C ECOACTL_isRd2Go Ready to Start UINT 0x015D ECOACTL_isRd2St Ready to Stop UINT 0x015E ECOACTL_isStart Started UINT 0x015F ECOACTL_isStop Stopped UINT...
  • Page 77 APPENDIX D — MODBUS CONFIGURATION (cont) ADDRESS DISPLAY VALUE REG. N° PARAMETER DESCRIPTION MODE TYPE UNIT COMMENT HEXADEC. DEC. MIN. MAX. DEFAULT (16BITS) 0x0198 OILPCTL_fWd Fault Word UINT 0x019A OILPCTL_isEnable Enable UINT 0x019B OILPCTL_isNom Nominal UINT 0x019C OILPCTL_isRd2Go Ready to Start UINT 0x019D OILPCTL_isRd2St...
  • Page 78 APPENDIX D — MODBUS CONFIGURATION (cont) ADDRESS DISPLAY VALUE REG. N° PARAMETER DESCRIPTION MODE TYPE UNIT COMMENT HEXADEC. DEC. MIN. MAX. DEFAULT (16BITS) 0x01DE CIRCACTL_ck1avscp cirAActualVarSpdComprCap FLOAT 0x01DF CIRCACTL_ck1rfcap cirARunFixSpdComprCap FLOAT 0x01E0 CIRCACTL_ck1rvcap cirARunVarSpdComprCap FLOAT 0x01E1 CIRCACTL_cmpn_wrd Compression A Diag Word UINT 0x01E3 CIRCACTL_status...
  • Page 79 VALUE REG. N° PARAMETER DESCRIPTION MODE TYPE UNIT COMMENT HEXADEC. DEC. MIN. MAX. DEFAULT (16BITS) MV: 0=None, 1=FS VFD, 2=Carrier, 3=Rockwell LF2, 0x0216 FACTORY_vfd_opt VFD Option UINT 4=Eaton, 5=Rockwell STD, 6=ABB, 7=Danfoss MV: 0=Disabled, 0x0217 FACTORY_exv_opt EXV Control Type UINT...
  • Page 80 HEXIDEC — Hexadecimal — HOLDING_REG_MEDIA — INPUT_REG_MEDIA — Multi-State Value © 2022 Carrier Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 04-53230018-01 Printed in U.S.A. Form 23XRV-1T...