Carrier AQUASNAP 30RB060-390 Controls, Start-Up, Operation, Service And Troubleshooting Instructions page 27

Air-cooled liquid chillers
Hide thumbs Also See for AQUASNAP 30RB060-390:
Table of Contents

Advertisement

Quick Commissioning with the Siemens VFD Operator
Panel (P0010=1) — It is important that parameter P0010 is
used for commissioning and P0003 is used to select the num-
ber of parameters to be accessed. The P0010 parameter allows
a group of parameters to be selected that will enable quick
commissioning. Parameters such as motor settings and ramp
settings are included. At the end of the quick commissioning
sequences, P3900 should be selected, which, when set to 1,
will carry out the necessary motor calculations and clear all
other parameters (not included in P0010=1 to the default set-
tings. This will only occur in Quick Commissioning mode. See
Fig. 16.
Reset the Siemens VFD to Factory Default — To reset all
parameters to the factory default settings; the following param-
eters should be set as follows:
1. Set P0010=30.
2. Set P0970 =1.
NOTE: The reset process can take up to 3 minutes to complete.
Table 21 — Siemens VFD Low Ambient Temperature Controller Operator Panel
PANEL/BUTTON
0
jog
Fn
P
FUNCTION
Indicates Status
The LCD displays the settings currently used by the converter.
Start Converter
The Start Converter button is disabled by default. To enable this button set P0700 = 1.
Stop Converter
Press the Stop Converter button to cause the motor to come to a standstill at the selected
ramp down rate. Disabled by default, to enable set P0700 = 1.
Press the Stop Converter button twice (or hold) to cause the motor to coast to a standstill.
This function is always enabled.
Change Direction
Press the Change Direction button to change the direction of rotation of the motor.
Reverse is indicated by a minus (–) sign or a flashing decimal point. Disabled by default, to
enable set P0700 = 1.
Jog Motor
Press the Jog Motor button while the inverter has no output to cause the motor to start and
run at the preset jog frequency. The motor stops when the button is released. The Jog
Motor button is not enabled when the motor is running.
Functions
The Functions button can be used to view additional information. Press and hold the but-
ton to display the following information starting from any parameter during operation:
1. DC link voltage (indicated by d – units V).
2. Output current. (A)
3. Output frequency (Hz)
4. Output voltage (indicated by o – units V).
5. The value selected in P0005 (If P0005 is set to show any of the above [3, 4, or 5] then
this will not be shown when toggling through the menu).
Press the Functions button repeatedly to toggle through displayed values.
Jump Function
Press of the Fn button from any parameter (rXXXX or PXXXX) to immediately jump to
R0000, when another parameter can be changed, if required. Return to R0000 and press
the Functions again to return.
Access Parameters
Allows access to the parameters.
Increase Value
Press the Increase Value button to increase the displayed value. To change the Frequency
Setpoint using the operator panel set P1000 = 1.
Decrease Value
Press the Decrease Value button to decrease the displayed value. To change the
Frequency Setpoint using the operating panel set P1000 = 1.
Troubleshooting the Siemens VFD with the Operating Panel
— Warnings and faults are displayed on the operating panel
with Axxx and Fxxx. The individual messages are shown in
Table 22.
If the motor fails to start, check the following:
• Power is present on T1, T2 and T3.
• Configuration jumpers are in place.
• Control signal between 1 vdc and 10 vdc is present on
terminals 3 and 4.
• P0010 = 0.
• P0700 = 2.
Siemens VFD Fault Messages (Tables 22 and 23) — In the
event of a failure, the drive switches off and a fault code ap-
pears on the display.
NOTE: To reset the fault code, one of the following methods
can be used:
1. Cycle the power to the drive.
2. Press the
button on the operator panel.
Fn
DESCRIPTION
27