Carrier AQUASNAP 30RB060-390 Controls, Start-Up, Operation, Service And Troubleshooting Instructions page 19

Air-cooled liquid chillers
Hide thumbs Also See for AQUASNAP 30RB060-390:
Table of Contents

Advertisement

MODE
KEYPAD ENTRY
CONFIGURATION
OPERATING MODES
NOTE: Bold values indicate sub-mode level.
Table 14 — Configuring the Slave Chiller
DISPLAY
DISP
ENTER
UNIT
SERV
OPTN
CCNA
CCN Address
ENTER
1
ENTER
1
ENTER
2
2
ENTER
CCNA
ESCAPE
CCNB
CCN Bus Number
0
ENTER
CCNB
ESCAPE
OPTN
ESCAPE
RSET
Reset Cool and Heat Tmp
CRST
Cooling Reset Type
ENTER
x 5
MSSL
Master/Slave Select
0
Disable
ENTER
0
Disable
ENTER
2
Slave
2
ENTER
MSSL
ESCAPE
SLVA
Slave Address
LLBL
Lead/Lag Balance Select
LLBD
Lead/Lag Balance Delta
LLDY
Lead/Lag Start Delay
LAGP
Lag Unit Pump Select
LPUL
Lead Pulldown Time
ESCAPE
ESCAPE
OPER
Operating Control Type
ENTER
0
Switch Control
ENTER
0
ENTER
2
CCN Control
2
ENTER
OPER
ESCAPE
ESCAPE
ITEM EXPANSION
Confirm address of chiller. The master and slave chiller
must have different addresses.
Factory default address is 1. The slave chiller address
must match what was programmed in the Master Chiller
SLVA item.
Flashing to indicate Edit Mode.
This item must match Master Chiller SLVA item.
Accepts the change.
Confirm the bus number of the chiller. The master and
slave chiller must be on the same bus.
Factory default bus number is 0.
Flashing to indicate Edit mode. May require Password
Use up arrows to change value to 2.
Accepts the change.
Not required.
Not required.
Not required.
Not required.
Must be configured to the same value as the master
chiller.
Not required.
At mode level
Flashing to indicate Edit Mode.
Use up arrows to change value to 2.
NOTE: Slave chiller must be configured for CCN.
Accepts the value.
At mode level
19