Operation; Sequence Of Operation; Dual Chiller Sequence Of Operation - Carrier AQUASNAP 30RB060-390 Controls, Start-Up, Operation, Service And Troubleshooting Instructions

Air-cooled liquid chillers
Hide thumbs Also See for AQUASNAP 30RB060-390:
Table of Contents

Advertisement

FLOW RATE REQUIREMENTS — Standard chillers should
be applied with nominal flow rates within those listed in the
Minimum and Maximum Cooler Flow Rates table. Higher or
lower flow rates are permissible to obtain lower or higher
temperature rises. Minimum flow rates must be exceeded to
assure turbulent flow and proper heat transfer in the cooler. See
Table 34.
CAUTION
Operation below minimum flow rate could subject tubes to
frost pinching in the tube sheet, resulting in failure of the
cooler.
Consult application data section in the Product Data
literature and job design requirements to determine flow rate
requirements for a particular installation.

OPERATION

Sequence of Operation —
the chiller, the cooler pump will start. After verifying water
flow, the control will monitor the entering and leaving water
temperature. At any time that a compressor is not operating, its
crankcase heater is active. If the need for mechanical cooling is
determined, the control decides which circuit and compressor
to start. The compressor will deenergize the crankcase heater as
it starts. Compressors will be staged with minimum load
control (if equipped and configured) to maintain LWT set
point.
Shutdown of each circuit under normal conditions occurs in
increments, starting with the minimum load control (if
MINIMUM
30RB
COOLER
SIZE
FLOW RATE
(gpm)
060
72
070
84
080
96
090
108
100
120
110
132
120
144
130
156
150
180
160
192
170
204
190
228
210
252
225
270
250
300
275
330
300
360
MINIMUM COOLER
FLOW RATE
30RB
(gpm)
SIZE
Module A
Module B
315
192
192
330
192
204
345
204
204
360
204
228
390
228
228
With a command to start
Table 34 — Minimum and Maximum Cooler Flow Rates
SIZES 060-300
MINIMUM
MAXIMUM
LOOP
FLOW RATE
VOLUME
(gpm)
(gal.)
288
180
336
210
384
240
432
270
480
300
528
330
576
360
624
390
720
450
768
480
816
510
912
570
1008
630
1080
675
1200
750
1320
825
1440
900
SIZES 315-390
MAXIMUM COOLER
FLOW RATE
(gpm)
VOLUME
Module A
Module B
768
768
768
816
816
816
816
912
912
912
equipped) and finishing with the last running compressor. Once
minimum load control is disabled, one compressor is
shut down. Eight seconds later the next compressor will
shut down. The process will continue until all of the compres-
sors are shut down. The EXV will close completely, 1 minute
after the last compressor has shut down. There are several
abnormal conditions that, if detected, will shut down the circuit
immediately. In this case, minimum load control and all
compressors are turned off without an 8-second interval
between them. The cooler pump will remain ON for 20 sec-
onds after the last compressor has been turned OFF.
Dual Chiller Sequence of Operation —
command to start the chiller, the master chiller determines
which chiller will become the lead chiller based on Configura-
tion
RSET
LLBL and Configuration
The lead chiller is always started first and the lag chiller is held
at zero percent capacity by the master chiller forcing the lag de-
mand limit value to 0%. The lead chiller's water pump will be
started. The lag chiller's water pump shall be maintained off if
Configuration
RSET
lead chiller will control capacity of the lead chiller.
If Lead Pulldown Time (Configuration
has been configured, the lead chiller will continue to operate
alone for that specified time. After the Lead Pulldown Time
timer has elapsed, if the lead chiller is fully loaded and either
all available compression is on or at the master demand limit
value, then the lag start timer (Configuration
LLDY) is initiated. When the pulldown timer and lag start
timer have elapsed and the Combined Leaving Chilled Water
Temperature is more than 3° F (1.7° C) above the set point,
then the lag chiller is started.
MINIMUM COOLER
FLOW RATE
(l/s)
5
5
6
7
8
8
9
10
11
12
13
14
16
17
19
21
23
MINIMUM COOLER
MIN
FLOW RATE
LOOP
(l/s)
(gal.)
Module A
Module B
945
12
12
990
12
13
1035
13
13
1080
13
14
1170
14
14
45

RSET
LAGP=0. The internal algorithm of

RSET
MAXIMUM
MINIMUM
COOLER
LOOP
FLOW RATE
VOLUME
(l/s)
(liters)
18
21
24
27
30
33
36
39
45
48
51
58
64
68
76
83
91
MAXIMUM COOLER
FLOW RATE
(l/s)
Module A
Module B
48
48
48
51
51
51
51
58
58
58
With
a
LLBD.
LPUL)
RSET
681
795
908
1022
1136
1249
1363
1476
1703
1817
1931
2158
2385
2555
2839
3123
3407
MIN
LOOP
VOLUME
(liters)
3577
3748
3918
4088
4429

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents