Carrier AQUASNAP 30RB060-390 Controls, Start-Up, Operation, Service And Troubleshooting Instructions page 18

Air-cooled liquid chillers
Hide thumbs Also See for AQUASNAP 30RB060-390:
Table of Contents

Advertisement

MODE
KEYPAD ENTRY
CONFIGURATION
OPERATING
MODES
NOTE: Bold values indicate sub-mode level.
Table 13 — Configuring the Master Chiller
DISPLAY
DISP
ENTER
UNIT
SERV
OPTN
ENTER
CCNA
CCN Address
ENTER
1
CCNA
ESCAPE
CCNB
CCN Bus Number
0
ENTER
CCNB
ESCAPE
OPTN
ESCAPE
Reset Cool and Heat Tmp
RSET
CRST
Cooling Reset Type
ENTER
x 5
MSSL
Master/Slave Select
0
Disable
ENTER
0
Disable
ENTER
1
Master
1
ENTER
MSSL
ESCAPE
SLVA
Slave Address
1
ENTER
1
ENTER
2
2
ENTER
SLVA
ESCAPE
LLBL
Lead/Lag Balance Select
ENBL
ENTER
LLBL
ESCAPE
LLBD
Lead/Lag Balance Delta
168
ENTER
LLBD
ESCAPE
LLDY
Lead/Lag Start Delay
10
ENTER
LLDY
ESCAPE
LAGP
Lag Unit Pump Select
0
Off if U Stp
ENTER
LAGP
ESCAPE
LPUL
Lead Pulldown Time
0
ENTER
ESCAPE
ESCAPE
Operating Control Type
OPER
ENTER
ENTER
0
Switch Control
ESCAPE
ITEM EXPANSION
Confirm address of chiller. The master and slave chiller
must have different addresses.
Factory default address is 1.
Confirm the bus number of the chiller. The master and slave
chiller must be on the same bus.
Factory default is 0.
Flashing to indicate Edit mode. May require Password.
Use up arrows to change value to 1.
Accepts the change.
Flashing to indicate Edit mode.
Use up arrows to change value to 2. This address must
match the address of the slave chiller.
Accepts the change.
Factory Default is ENBL
Factory Default is 168.
Factory Default is 10.
Factory Default is 0, Off if unit is stopped. Master and slave
chiller must be configured to the same value.
Factory Default is 0.
At mode level.
Master chiller should be configured for job requirements,
Switch Control, Time Schedule, or CCN.
At mode level.
18