Carrier AQUASNAP 30RB060-390 Controls, Start-Up, Operation, Service And Troubleshooting Instructions page 29

Air-cooled liquid chillers
Hide thumbs Also See for AQUASNAP 30RB060-390:
Table of Contents

Advertisement

Table 22 — Siemens VFD Low Ambient Temperature Controller Fault Messages
FAULT
F0001
• Motor power does not correspond to the
Overcurrent
inverter power
• Motor lead short circuit
• Ground fault
F0002
• DC-link voltage (r0026) exceeds trip level
Overvoltage
(P2172)
• Overvoltage can be caused either by too high
main supply voltage or if motor is in regenera-
tive mode
• Regenerative mode can be caused by fast
ramp downs or if the motor is driven from an
active load
F0003
• Main supply failed
Undervoltage
• Shock load outside specified limits
F0004
• Ambient temperature outside of limits
Drive
• Fan failure
Overtemperature
F0005
• Drive overloaded
2
Drive I
t
• Duty cycle too demanding
• Motor power (P0307) exceeds drive power
capability (P0206)
F0011
• Motor overloaded
Motor
• Motor data incorrect
2
Overtemperature I
t
• Long time period operating at low speeds
F0041
Stator resistance measurement failure
Stator Resistance
Measurement Failure
F0051
Reading or writing of the non-volatile parameter
Parameter EEPROM Fault
storage has failed
F0052
Reading of the powerstack information has
Powerstack Fault
failed or the data is invalid
F0060
Internal communications failure
Asic Timeout
F0070
No setpoint received from communications
Communications
board during telegram off time
Board Setpoint Error
F0071
No response during telegram off time via USS
No Data for USS (RS232
(BOP link)
Link) During
Telegram Off Time
F0072
No response during telegram off time via USS
No Data from USS (RS485
(COM link)
Link) During
Telegram Off Time
F0080
• Broken wire
Analog Input -
• Signal out of limits
Lost Input Signal
F0085
External fault is triggered via terminal inputs
External Fault
F0101
Software error or processor failure
Stack Overflow
F0221
PID Feedback below minimum value P2268
PI Feedback
Below Minimum Value
F0222
PID Feedback above maximum value P2267
PI Feedback Above
Maximum Value
F0450
Fault value
(Service Mode Only)
1
Some of the power section tests have failed
BIST Tests Failure
2
Some of the control board tests have failed
4
Some of the functional tests have failed
8
Some of the IO module tests have failed
16 The Internal RAM has failed its check on
power-up
LEGEND
I
2
t — Current Squared Time
POSSIBLE CAUSES
TROUBLESHOOTING
Check the following:
1. Motor power (P0307) must correspond to inverter power (P0206)
2. Motor cable and motor must have no short-circuits or ground faults
3. Motor parameters must match the motor in use
4. Motor must not be obstructed or overloaded
After Steps 1-4 have been checked, increase the ramp time (P1120) and reduce the
boost level (P1310, P1311, P1312).
Check the following:
1. Supply voltage (P0210) must lie within limits indicated on rating plate
2. DC-link voltage controller must be enabled (P1240) and have parameters set
correctly
3. Ramp-down time (P1121) must match inertia of load
Check the following:
1. Supply voltage (P0210) must lie within limits indicated on rating plate
2. Supply must not be susceptible to temporary failures or voltage reductions
Check the following:
1. Fan must turn when inverter is running
2. Pulse frequency must be set to default value
3. Air inlet and outlet points are not obstructed
4. Ambient temperature could be higher than specified for the drive.
Check the following:
1. Load duty cycle must lie within specified limits
2. Motor power (P0307) must match drive power (P0206)
1. Check motor data
2. Check loading on motor
3. Boost settings too high (P1310, P1311, P1312)
4. Check parameter for motor thermal time constant
2
5. Check parameter for motor I
t warning level
1. Check if the motor is connected to the drive
2. Check that the motor data has been entered correctly
1. Factory reset and new parameters set
2. Replace drive
Replace drive
1. Acknowledge fault
2. Replace drive if repeated
1. Check connections to the communications board
2. Check the master
1. Check connections to the communications board
2. Check the master
1. Check connections to the communications board
2. Check the master
Check connection to analog input
Disable terminal input for fault trigger
1. Run self test routines
2. Replace drive
1. Change value of P2268
2. Adjust feedback gain
1. Change value of P2267
2. Adjust feedback gain
1. Inverter may run but certain actions will not function correctly
2. Replace drive
29