Carrier AQUASNAP 30RB060-390 Controls, Start-Up, Operation, Service And Troubleshooting Instructions page 106

Air-cooled liquid chillers
Hide thumbs Also See for AQUASNAP 30RB060-390:
Table of Contents

Advertisement

TABLE
DISPLAY NAME
CP_UNABL
Compressor A1 Disable
Compressor A2 Disable
Compressor A3 Disable
Compressor A4 Disable
Compressor B1 Disable
Compressor B2 Disable
Compressor B3 Disable
Compressor B4 Disable
Compressor C1 Disable
Compressor C2 Disable
Compressor C3 Disable
Compressor C4 Disable
NOTES:
1. Table used to disable compressors for maintenance purposes.
The capacity control will consider that these compressors (once
set to YES) are failed manually (no alarm will appear).
TABLE
DISPLAY NAME
MAINTENANCE CONFIG
MAINTCFG
Servicing Alert
Refrigerant Charge Ctrl
Water Loop Control
CPump 1 Ctl Delay (days) 0-1000
CPump 2 Ctl Delay (days) 0-1000
HPump Ctrl Delay (days)
Water Filter Ctrl (days)
TABLE
DISPLAY NAME
SERVICE1
Cooler Fluid Type
Entering Fluid Control
Prop PID Gain Varifan
Int PID Gain Varifan
Deri PID Gain Varifan
EXV A Superheat Setpoint
EXV B Superheat Setpoint
EXV C Superheat Setpoint
EXV MOP Setpoint
High Pressure Threshold
Cooler Heater Delta Spt
Brine Freeze Setpoint
Minimum LWT Setpoint
Auto Start When SM Lost
Auto Z Multiplier Setpt
Maximum Z Multiplier
Recl Valve Min Position
Recl Valve Max Position
User Password
Service Password
SPM Board Configuration
Maximum Ducted Fan Speed 0-100
NOTE: This table shall be downloadable at any time. However, modified value shall not be used by tasks until the unit is in OFF state. This shall not
apply to the Varifan gains that shall be modified at any time and used immediately by the head pressure control tasks even if the unit is in operation.
APPENDIX B — CCN TABLES (cont)
SERVICE DISPLAY TABLES
RANGE
DEFAULT
No/Yes
No
No/Yes
No
No/Yes
No
No/Yes
No
No/Yes
No
No/Yes
No
No/Yes
No
No/Yes
No
No/Yes
No
No/Yes
No
No/Yes
No
No/Yes
No
RANGE
DEFAULT
Enable/Disable
Disable
Enable/Disable
Disable
Enable/Disable
Disable
0
0
0-1000
0
0-1000
0
RANGE
DEFAULT
1-3
1
Yes/No
No
–20.0-20.0
2.0
–5.0-5.0
0.2
–20.0-20.0
0.4
2.5-54.0
9.0
2.5-54.0
9.0
2.5-54.0
9.0
30.8-50.0
50.0
500-640
609
1-6
2
–20-34
34
38
Enable/Disable
Disable
4-10
6
1.0-6.0
6.0
0-50
20
20-100
100
0-150
11
0-150
88
0 or 1 for each digit 00001010
100
106
UNITS
un_cp_a1
un_cp_a2
un_cp_a3
un_cp_a4
un_cp_b1
un_cp_b2
un_cp_b3
un_cp_b4
un_cp_c1
un_cp_c2
un_cp_c3
un_cp_c4
2. All data will be re-initialized to "NO" at Power on reset on units
using pro_dialog display. For ComfortLink™ display, data shall be
saved.
UNITS
s_alert
charge_c
wloop_c
cpump1_c
cpump2_c
hpump_c
wfilte_c
UNITS
POINT NAME
flui_typ
ewt_opt
hd_pg
hd_ig
hd_dg
^F
sh_sp_a
^F
sh_sp_b
^F
sh_sp_c
°F
mop_sp
psi
hp_th
^F
heatersp
°F
lowestsp
°F
mini_lwt
auto_sm
zm_spt
hc_zm
%
min_3w
%
max_3w
N/A
use_pass
N/A
ser_pass
spm_conf
%
fan_max
POINT NAME
WRITE STATUS
POINT NAME
WRITE STATUS
WRITE STATUS