Communicating With Plc; Step 1. Preparing Plc & Pc - Omron WE70-AP Operation Manual

Fa wireless lan unit
Table of Contents

Advertisement

Chapter 3 Basic Setup

3-5. Communicating with PLC

This section describes how to set communication between an access point (WE70-AP) and a client (WE70-
CL).A PLC + Ethernet unit must be connected to an access point using a LAN cable.PC with Ethernet card
must be connected to a client (WE70-CL).
Step 1. Preparing PLC & PC
PLC is connected to Access point using straight LAN cable.
3
A client (slave) can be configured by direct connection of a LAN cable or wireless connection by entering
"192.168.0.254" (factory shipment setting) to PC connected to an access point.
To connect a PLC to an Ethernet network, 100BASE-TX type Ethernet unit CS1W-ETN21 or CJ1W-ETN21
is required.
CS series Ethernet unit
(CS1W-ETN21)
CJ series Ethernet unit
(CJ1W-ETN21)
LAN Cable
3-20
Straight LAN cable
Straight LAN cable
Network Device
Access Point
WE70-AP
PLC + Ethernet unit
Description
A communication unit to connect a CS series or
CJ series PLC to a 100BASE-TX type Ethernet
network.
A LAN cable with RJ45 modular connectors on
both ends,used to connect a 100BASE-TX type
Ethernet unit and an access point.
An STP (shielded twisted pair) cable of category
3, 4, 5, or 5e must be used.